3-158
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
stVal
ENUMERATED
ST
1 (on)
R
ctlModel
CtlModels
CF
0 (status only)
R
Health
INS
This logical node’s health
R
stVal
ENUMERATED
ST LPHD1.PhyHealth.stVal
R
Loc
SPS
Value of operand selected by setting
XCBR# ST.LOC OPERAND
R
stVal
BOOLEAN
ST Bkr0XCBR#.Loc.stVal
R
OpCnt
INS
Phase
ψ
breaker operations counter.
R
stVal
INT32
ST
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1
R
units.multiplier
ENUMERATED
0
R
BadSt1
SPS
BREAKER #
ψ
BAD ST operand
R
stVal
BOOLEAN
ST BREAKER #
ψ
BAD ST
R
ClsSt1
SPS
BREAKER #
ψ
CLSD operand
R
stVal
BOOLEAN
ST BREAKER #
ψ
CLSD
R
OpnSt1
SPS
BREAKER #
ψ
OPEN operand
R
stVal
BOOLEAN
ST BREAKER #
ψ
OPEN
R
IntermSt1
SPS
BREAKER #
ψ
INTERM operand
R
stVal
BOOLEAN
ST BREAKER #
ψ
INTERM
R
Pos
DPC
Breaker
φψ
position status
R
stVal
CODED ENUM
ST
R
ctlModel
CtlModels
CF
0
R
BlkOpn
SPC
Breaker open commands blocked from
all sources including protection
R
stVal
BOOLEAN
ST Bkr0XCBR#.BlkOpn.stVal
R
ctlModel
CtlModels
CF
0
R
BlkCls
SPC
Breaker close commands blocked from
all sources including protection
R
stVal
BOOLEAN
ST Bkr0XCBR#.BlkCls.stVal
R
ctlModel
CtlModels
CF
0
R
CBOpCap
INS
Mandatory data object which in this case
is fixed at 3
R
stVal
ENUMERATED
ST
3
R
InRef1
ORG
BREAKER #
φ
A/3P CLSD setting” if
Θ
=”1”,
“BREAKER #
φ
B CLSD setting” if
Θ
=”2”, or
“BREAKER #
φ
C CLSD setting” if
Θ
=”3
R
GEORG
R
setSrcRef
ObjectReference SP BREAKER #
φ
A/3P CLSD if
Θ
=”1”,
BREAKER #
φ
B CLSD if
Θ
=”2”, or
BREAKER #
φ
C CLSD if
Θ
=”3”
reference to the data attribute to input
R/C
VISIBLE
STRING255
SP
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs
VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName
VISIBLE
STRING255
EX GEORG
R
InRef2
ORG
BREAKER #
φ
A/3P OPND setting” if
Θ
=”1”,
“BREAKER #
φ
B OPND setting” if
Θ
=”2”, or
“BREAKER #
φ
C OPND setting” if
Θ
=”3
R
GEORG
R
LNName: Bkr
Θ
XCBR#
LDevice inst: System
UR element: Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C