CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-127
3
3.5.3.10 Cold load pickup (Cold)
This element is instantiated in the following products: F35, F60.
Table 3-145: Cold load pickup data objects
InRef24
ORG
CAP # LOCAL OPEN setting.
R
setSrcRef
ObjectReference SP CAP # LOCAL OPEN setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef25
ORG
CAP # AUTO OPEN setting.
R
setSrcRef
ObjectReference SP CAP # AUTO OPEN setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef26
ORG
CAP # BKR OPEN 52b setting.
R
setSrcRef
ObjectReference SP CAP # BKR OPEN 52b setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef27
ORG
CAP # REMOTE CLOSE setting.
R
setSrcRef
ObjectReference SP CAP # REMOTE CLOSE setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef28
ORG
CAP # LOCAL CLOSE setting.
R
setSrcRef
ObjectReference SP CAP # LOCAL CLOSE setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef29
ORG
CAP # AUTO CLOSE setting.
R
setSrcRef
ObjectReference SP CAP # AUTO CLOSE setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef30
ORG
CAP # BKR CLSD 52a setting.
R
setSrcRef
ObjectReference SP CAP # BKR CLSD 52a setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
BlkRef1
ORG
CAP # BKR CLOSE BLK setting.
R
setSrcRef
ObjectReference SP CAP # BKR CLOSE BLK
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef31
ORG
CAP # CLS OVERRIDE setting.
R
setSrcRef
ObjectReference SP CAP # CLS OVERRIDE setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: ColdFXUT#
LDevice inst: Ctrl
UR element: Cold Load Pickup # element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
COLD LOAD # OP operand
R
general
BOOLEAN
ST COLD LOAD # OP
R
StrVal
ASG
Start level of the current, which is fixed at
2% of Nominal CT (0.02 pu), and it is non-
configurable read only value
R
setMag
AnalogueValue SP
R
setMag.f
FLOAT32
0.02
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
BlkRef1
ORG
COLD LOAD # BLK setting
R
setSrcRef
ObjectReference SP COLD LOAD # BLK.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef1
ORG
COLD LOAD # INIT setting
R
setSrcRef
ObjectReference SP COLD LOAD # INIT.
reference to the data attribute to input
R/C
LNName: CapCtlGAPC#
LDevice inst: Ctrl
UR element: Capacitor control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C