3-68
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.32 Line pickup (LinPkp)
This element is instantiated in the following products: D30, D60, L60, L90.
Table 3-59: Line pickup data objects
3.5.2.33 Load encroachment (LodEn)
This element is instantiated in the following products: D30, D60, F60, L60, L90, T60.
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
TERMINAL 2 I
θ
magnitude, in
primary amps
R
phs
θ
.instCVal.ang
.f
FLOAT32
TERMINAL 2
UR range -180...+180 converted to 0...360R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
TERMINAL 2 I
θ
magnitude, in
primary amps, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
TERMINAL 2
UR range -180...+180 converted to 0...360R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit ENUMERATED
5, the code for amps
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF LinDf2MMXU1.A.phs
θ
.db
R/W/C
phs
θ
.dbAng
INT32U
CF LinDf2MMXU1.A.phs
θ
.dbAng
R/W/C
phs
θ
.zeroDb
INT32U
CF CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
LNName: LinPkpPIOC1
LDevice inst: Prot
UR element: Line Pickup functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
LINE PICKUP PKP operand
R
general
BOOLEAN
ST LINE PICKUP PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
Op
ACT
LINE PICKUP OP operand
R
general
BOOLEAN
ST LINE PICKUP OP
R
Dpo
SPS
LINE PICKUP DPO operand, which is the
inverse of LINE PICKUP PKP
R
stVal
BOOLEAN
ST LINE PICKUP DPO
R
UnA
φ
SPS
LINE PICKUP operand that activates on
phase
θ
current below 5% of nominal
R
stVal
BOOLEAN
ST LINE PICKUP I<
θ
R
UnV
SPS
LINE PICKUP UV PKP operand
R
stVal
BOOLEAN
ST LINE PICKUP UV PKP
R
LeoSt
SPS
LINE PICKUP LEO PKP operand
R
stVal
BOOLEAN
ST LINE PICKUP LEO PKP
R
Zn2Tr
SPS
LINE PICKUP RCL TRIP operand
R
stVal
BOOLEAN
ST LINE PICKUP RCL TRIP
R
BlkRef
γ
ORG
LINE PICKUP BLOCK setting for setting
group
γ
.
R
setSrcRef
ObjectReference SP LINE PICKUP BLOCK for group
γ
. reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: LinDf2MMXU1
LDevice inst: Prot
UR element: Line Differential element (ANSI 87L) – terminal 2 current
function
data obj. data attribute
Type
FC UR Name
Description
R/W/C