CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-159
3
3.5.4.4 B90 isolator monitoring (B_Iso)
This element is instantiated in the following products: B90.
Table 3-174: B90 isolator monitoring data objects
3.5.4.5 Contact input interface (ConIn)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-175: Contact input data objects
setSrcRef
ObjectReference SP BREAKER #
φ
A/3P OPND if
Θ
=”1”,
BREAKER #
φ
B OPND if
Θ
=”2”, or
BREAKER #
φ
C OPND if
Θ
=”3”
reference to the data attribute to input
R/C
VISIBLE
STRING255
SP
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs
VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName
VISIBLE
STRING255
EX GEORG
R
LNName: B_IsoSSWI#
LDevice inst: System
UR element: B90 ISOLATOR # function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
OpTmAlm
SPS
ISOLATOR # ALARM operand.
R
stVal
BOOLEAN
ST ISOLATOR # ALARM
R
IsoPos
ACT
ISOLATOR # POSITION operand.
R
general
BOOLEAN
ST ISOLATOR # POSITION
R
IsoBlk
ACT
ISOLATOR # BLOCK OP operand.
R
general
BOOLEAN
ST ISOLATOR # BLOCK
R
InRef1
ORG
ISOLATOR # OPEN setting.
R
setSrcRef
ObjectReference SP ISOLATOR # OPEN
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef2
ORG
ISOLATOR # CLOSED setting.
R
setSrcRef
ObjectReference SP ISOLATOR # CLOSED
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef3
ORG
ISOLATOR # RESET setting
R
setSrcRef
ObjectReference SP ISOLATOR # RESET.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: ConInGGIO1
LDevice inst: System
UR element: Contact Inputs
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Mod
INC
This logical node’s mode
R/Ctrl
stVal
ENUMERATED
ST
1 (on)
R
ctlModel
CtlModels
CF
0 (status only)
R
Health
INS
This logical node’s health
R
stVal
ENUMERATED
ST LPHD1.PhyHealth.stVal
R
Ind1
Θ
SPS
Con Ip
Θ
On (
φ
) operand value
R
stVal
BOOLEAN
ST Cont Ip
φ
On
R
LNName: Bkr
Θ
XCBR#
LDevice inst: System
UR element: Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C