3-152
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.4.2 AC inputs (CT inputs and VT inputs) (ACin)
Uses Beh and NamPlt elements outlined in the
Common data objects and attributes table on page 3-29
.
3.5.4.3 Breaker control (Bkr)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-170: Breaker control data objects
Table 3-171: Breaker control data objects
LNName: BkrCSWI#
LDevice inst: System
UR element: Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Mod
INC
This logical node’s mode
R/Ctrl
stVal
ENUMERATED
ST
1 (on)
R
ctlModel
CtlModels
CF
0 (status only)
R
Health
INS
This logical node’s health
R
stVal
ENUMERATED
ST LPHD1.PhyHealth.stVal
R
Pos
DPC
Breaker position control and status
R/Ctrl
stVal
CODED ENUM
ST Bkr0XCBR#.Pos.stVal
R
stSeld
BOOLEAN
ST
The controllable data status is “selected” R
pulseConfig
PulseConfig
CF
R
pulseConfig
.cmdQual
ENUMERATED
0 (pulse)
R
pulseConfig.onDur INT32U
2
R
pulseConfig
.offDur
INT32U
0
R
pulseConfig
.numPls
INT32U
1
R
ctlModel
CtlModels
CF BkrCSWI# Pos ctlModel
R/W/C
sboTimeout
INT32U
CF BkrCSWI# Pos sboTimeout
R/W/C
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF BkrCSWI# Pos operTimeout
R/C
LNName: BkrCILO#
LDevice inst: System
UR element: Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Mod
INC
This logical node’s mode
R/Ctrl
stVal
ENUMERATED
ST
1 (on)
R
ctlModel
CtlModels
CF
0 (status only)
R
Health
INS
This logical node’s health
R
stVal
ENUMERATED
ST LPHD1.PhyHealth.stVal
R
EnaOpn
SPS
Enable Open status
R
stVal
BOOLEAN
ST
The state of the operand selected by
setting XCBR# INTERLOCK OPN
R
EnaCls
SPS
Enable Close status
R
stVal
BOOLEAN
ST
Logical OR of the state of the operand
selected by setting XCBR# SYNCCHECK
CLS and the state of the operand selected
by setting XCBR# INTERLOCK CLS
R
InRef2
ORG
XCBR# INTERLOCK OPN setting.
R
GEORG
R
setSrcRef
ObjectReference SP XCBR# INTERLOCK OPN
reference to the data attribute to input
R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
XCBR# INTERLOCK OPN
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C