CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-217
3
LocSetAcsOff
SPS
Indicates operations of FlexLogic operand ACCESS LOC SETG OFF
SecGSAL
LocSetAcsOn
SPS
Indicates operations of FlexLogic operand ACCESS LOC SETG ON
SecGSAL
LosLife
MV
XFMR LIFE LOST actual values
LosLifSPTR
LosLifeRte
MV
DAILY RATE LOL actual values
LosLifSPTR
LosPkt1
SPS
The lost packet threshold has been exceeded.
The 87L DIFF CH 1 LOSTPKT operand, which becomes On when the differential
element has detected the lost packet threshold has been exceeded on channel 1.
LinDfPDIF
LossLd
ACT
The high impedance fault phase A, B, C loss of load element has operated
HiZPHIZ
Lower
SPS
PID Lower operand. The PID 1 LOWER operand value.
PIDRegFPID
MAC
VSG
Expected value of Destination MAC address field in messages subscribed to by
RxGOOSE#
LGOS
MajorErr
SPS
Any of the major self-test errors generated (major error).
The ANY MAJOR ERROR operand.
LPHD
ManMod
SPS
Capacitor control in manual mode.
The CAP 1 IN MAN operand.
CapCtlGAPC
MaxAsymOp1
SPS
Asymmetry on the channel exceeded pre-set value.
The 87L DIFF CH 1 MAX ASYM operand, which becomes On when the Asymmetry
on channel 1 exceeded preset value.
LinDfPDIF
MaxCompHz
MV
The frequency of the learned maximum broken rotor bar spectral component.
MAXIMUM COMPONENT FREQ. in Hz.
BknRotSVBR
MaxCompLevel MV
Indicates the learned maximum level of the broken rotor bar spectral component
since the last data clear.
MAXIMUM COMPONENT LEVEL in dB.
BknRotSVBR
MaxIntrA
MV
Indicates Breaker Arcing Current per phase.
BKR 1 AMP MAX phase A/B/C.
CBArc
Θ
SCBR
MaxLoadDev
MV
Indicates the motor load standard deviation at the time when data for the
maximum broken rotor bar was acquired.
LOAD DEV. AT BRB MAX in x FLA.
BknRotSVBR
MaxMotLoad
MV
Indicates the average motor load at the time when data for the maximum broken
rotor bar was acquired.
MOTOR LOAD AT BRB MAX in x FLA.
BknRotSVBR
MaxVal1
ASG
Maximum value in deadband calculations
TDCInGGIO1,
TDCOutGGIO1
MinorErr
SPS
Any of the minor self-test errors generated (minor error).
The ANY MINOR ERROR operand.
LPHD
MinVal1
ASG
Minimum value in deadband calculations
TDCInGGIO1,
TDCOutGGIO1
MMSConnects
MV
Number of MMS client connections active
LPHD
MnlCls
SPS
Manual close initiated.
The BREAKER 1 MNL CLS operand.
Bkr0XCBR
MnlOpn
SPS
Manual open initiated.
The BREAKER 1 MNL OPEN operand.
Bkr0XCBR
Month1
SPS
Current month, where 1 = January.
The MONTH operand.
TmDayGAPC
MotLoad
MV
The average motor load at the time of the broken rotor bar data acquisition stage.
MOTOR LOAD AT BRB CALC. in x FLA
BknRotSVBR
MotStatus
ENS
Indicated the status of the motor (in Actual Values) where 0 = Offline, 1= Starting,
2 = Running and 3 = Overload.
Thermal Model MOTOR STATUS.
MotThmPTTR
MotUnb
MV
% thermal model motor unbalance.
THERMAL MODEL MOTOR UNBALANCE in percentage (%).
MotThmPTTR
NegTotVArh
MV
SRC 1 Total VAr-hour in negative direction
EnrMtrMMTR
NegTotWh
MV
SRC 1 Total Watt-hour in negative direction
EnrMtrMMTR
NeutOpn
SPS
Indicates source has lost voltage signal.
The SRC1 VT NEU WIRE OPEN operand.
VtffGAPC
Data object
name
CDC
Semantics
Used in logical nodes…