3-94
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.58 Phase instantaneous overcurrent (PhsIoc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60.
Table 3-103: Phase instantaneous overcurrent data objects
DpoPhs
φ
SPS
PHS DIST Z# DPO
θ
operand in Phase-To-
Phase
R
stVal
BOOLEAN
ST PHS DIST Z# DPO
θ
R
OpPhs
φ
SPS
PH DIST Z # OP
θ
operand
R
stVal
BOOLEAN
ST PH DIST Z# OP
θ
R
ASupn
φ
SPS
PHS DIST Z# SUPN
θ
operand in Phase-
To-Phase
R
stVal
BOOLEAN
ST PHS DIST Z# SUPN
θ
R
BlkRef
γ
ORG
PHS DIST Z# BLK setting for setting group
γ
.
R
setSrcRef
ObjectReference SP PHS DIST Z# BLK.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef
γ
2
ORG
instantiated only in logical node instance
1
R
setSrcRef
ObjectReference SP setting FORCE SELF-POLAR
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef
γ
3
ORG
instantiated only in logical node instance
1
R
setSrcRef
ObjectReference SP setting FORCE MEM-POLAR l
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: PhsIocPIOC#
LDevice inst: Prot
UR element: Phase Instantaneous Overcurrent element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
PHASE IOC# PKP operands (including
individual three phases), which indicates
Op will operate when delay expires
R
general
BOOLEAN
ST PHASE IOC# PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
phsA
BOOLEAN
ST PHASE IOC# PKP A
R
dirPhsA
ENUMERATED
ST
0, the code for unknown
R
phsB
BOOLEAN
ST PHASE IOC# PKP B
R
dirPhsB
ENUMERATED
ST
0, the code for unknown
R
phsC
BOOLEAN
ST PHASE IOC# PKP C
R
dirPhsC
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
PHASE IOC# OP operands (including
individual three phases)
R
general
BOOLEAN
ST PHASE IOC# OP
R
phsA
BOOLEAN
ST PHASE IOC# OP A
R
phsB
BOOLEAN
ST PHASE IOC# OP B
R
phsC
BOOLEAN
ST PHASE IOC# OP C
R
Dpo
SPS
PHASE IOC# DPO operand
R
stVal
BOOLEAN
ST PHASE IOC# DPO
R
DpoPhs
β
SPS
PHASE IOC# DPO
β
operands” (where
β
refers to Phase-A, B or C)
R
stVal
BOOLEAN
ST PHASE IOC# DPO
β
(where
β
refers to Phase-A, B or C)
R
BlkRef
γβ
ORG
PHASE IOC# BLOCK
β
setting for setting
group
γ
.” (where
β
refers to Phase-A, B or
C)
R
setSrcRef
ObjectReference SP PHASE IOC# BLOCK
β
(where
β
refers to Phase-A, B or C)
reference to the data attribute to input
R/C
LNName: PhsDisPDIS#
LDevice inst: Prot
UR element: Phase Distance Z# settings
data obj. data attribute
Type
FC UR Name
Description
R/W/C