3-62
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.30 Hybrid permissive over-reaching transfer trip (HPOTT_)
This element is instantiated in the following products: D60, L90.
Table 3-54: Hybrid POTT data objects
Op
ACT
GROUND TOC# OP operand
R
general
BOOLEAN
ST GROUND TOC# OP
R
Dpo
SPS
GROUND TOC# DPO operand
R
stVal
BOOLEAN
ST GROUND TOC# DPO
R
BlkRef
γ
1
ORG
GROUND TOC# BLOCK setting in setting
group
γ
.
R
setSrcRef
ObjectReference SP GROUND TOC# BLOCK.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: HPOTT_PSCH1
LDevice inst: Prot
UR element: Hybrid Permissive Over-reaching Transfer Trip element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
HYBRID POTT OP operand
R
general
BOOLEAN
ST HYBRID POTT OP
R
phsA
BOOLEAN
ST HYBRID POTT TRIP A
R
phsB
BOOLEAN
ST HYBRID POTT TRIP B
R
phsC
BOOLEAN
ST HYBRID POTT TRIP C
R
Tr3p
ACT
HYBRID POTT TRIP 3P operand
R
general
BOOLEAN
ST HYBRID POTT TRIP 3P
R
Tx1
SPS
HYBRID POTT TX1 operand
R
stVal
BOOLEAN
ST HYBRID POTT TX1
R
Tx2
SPS
HYBRID POTT TX2 operand
R
stVal
BOOLEAN
ST HYBRID POTT TX2
R
Tx3
SPS
HYBRID POTT TX3 operand
R
stVal
BOOLEAN
ST HYBRID POTT TX3
R
Tx4
SPS
HYBRID POTT TX4 operand
R
stVal
BOOLEAN
ST HYBRID POTT TX4
R
BlkRef1
ORG
HYB POTT SCHEME BLOCK setting
R
setSrcRef
ObjectReference SP HYB POTT SCHEME BLOCK
Reference to the data attribute to input R/C
setSrcCB
ObjectReference SP
Source GoCB of input if via GOOSE
R/C
InRef5
ORG
HYB POTT ECHO COND setting
R
setSrcRef
ObjectReference SP HYB POTT ECHO COND
Reference to the data attribute to input R/C
setSrcCB
ObjectReference SP
Source GoCB of input if via GOOSE
R/C
InRef8
ORG
HYB POTT W/I COND setting
R
setSrcRef
ObjectReference SP HYB POTT W/I COND
Reference to the data attribute to input R/C
setSrcCB
ObjectReference SP
Source GoCB of input if via GOOSE
R/C
InRef6
ORG
GND DIR O/C FWD setting
R
setSrcRef
ObjectReference SP GND DIR O/C FWD
Reference to the data attribute to input R/C
setSrcCB
ObjectReference SP
Source GoCB of input if via GOOSE
R/C
InRef7
ORG
GND DIR O/C REV setting
R
setSrcRef
ObjectReference SP GND DIR O/C REV
Reference to the data attribute to input R/C
setSrcCB
ObjectReference SP
Source GoCB of input if via GOOSE
R/C
InRef1
ORG
HYB POTT RX1 setting
R
setSrcRef
ObjectReference SP HYB POTT RX1
Reference to the data attribute to input R/C
setSrcCB
ObjectReference SP
Source GoCB of input if via GOOSE
R/C
InRef2
ORG
HYB POTT RX2 setting
R
LNName: GndTocPTOC#
LDevice inst: Prot
UR element: Ground Time Overcurrent element#
data obj. data attribute
Type
FC UR Name
Description
R/W/C