3-220
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
RlyUTCTms
INS
Represents the relay UTC time in seconds elapsed since 00:00:00 January 1, 1970.
Mapped to Modbus register 41A0h value, that is, "Relay time clock set time"
register value after converting to UTC (if time zone and DST is used).
LPHD
RrtdComFail
SPS
RRTD communication failure.
The RRTD COMM FAIL operand.
LPHD
Rs
SPS
Autoreclose has been reset either manually or by the rest timer.
The AR RESET operand.
Rec13pRREC
RsOp
SPS
Target resetting - General indication (binary input).
The RESET OP operand value.
TgtRsIHMI
RsOpLoc
SPS
Target resetting - General indication (binary input).
The RESET OP (OPERAND) operand value.
TgtRsIHMI
RsOpPB
SPS
Target resetting - General indication (binary input).
The RESET OP (PUSHBUTTON) operand value.
TgtRsIHMI
RsOpRem
SPS
Target resetting - General indication (binary input).
The RESET OP (COMMS) operand value.
TgtRsIHMI
RsTms
INS
The UTC time of the last clear in seconds elapsed since 00:00:00 January 1, 1970.
The LAST CLEARED DATE actual value.
OscRDRE
RtdTrbl
SPS
RTD trouble.
The RTD TROUBLE operand.
LPHD
Running
SPS
Indicate the motor is running.
The MOTOR RUNNING operand.
MotThmPTTR
RvOp
SPS
Fault direction is reverse.
The NEG SEQ DIR OC1 REV operand.
The NTRL DIR OC1 REV operand.
NegDocRDIR, NeuDocRDIR
RX1
SPS
Pulse received on channel 1 or 2.
The 87PC RX1 operand.
PhCmp1PDIF
RxGooseOff
SPS
One or more RxGOOSE is not responding.
The RxGOOSE OFF operand.
LPHD
Sat1
SPS
Indicates CT saturation is detected.
The BUS 1 SAT A/B/C operand.
B_DifPDIF, BusDifPDIF
Sat1
SPS
Indicates phase saturation of differential is detected per phase
The STATOR DIFF1 SAT A/B/C operand.
SttDifPDIF
SbstCls
SPS
Manually substituted to close.
The BREAKER 1 SUBD CLSD operand.
Bkr0XCBR
SbstOpn
SPS
Manually substituted to open.
The BREAKER 1 SUBD OPEN operand.
Bkr0XCBR
SecDataClr
SPC
Command CLEAR SECURITY DATA, TRUE = CLEAR SECURITY DATA
SecGSAL
SecEna
ENG
RxRGOOSE1 Security Ena setting: 0=None; 1=Signature; 2=Signature and
Encryption. Otherwise ignored.
LGOS
SecEthFail
SPS
Second Ethernet failure.
The SECOND ETHERNET FAIL operand.
LPHD
SecondOfDay
INS
Represents integer number of seconds past midnight (Range1-86400).
The SecondOfDay actual value in seconds.
TmDayGAPC
SeqTO
SPS
The incomplete sequence timer timed out.
The AR INCOMPLETE SEQ operand.
Rec13pRREC
SHAmpAng
MV
Sub harmonic current angle.
SH CURRENT ANGLE in degrees.
SubHaPHIZ
ShotCnt1
SPS
Autoreclosec shot count is equal to the number indicated by the data instance
number.
The AR SHOT CNT=1 operand.
Rec13pRREC, Rec3pRREC
ShrtCirc
SPS
Short circuit detected.
The RRTD RTD 1 SHORTED operand.
The RTD Ip 1 SHORTED operand.
PRTDsSTMP, RRTDsSTMP
Sim
SPC
Simulated GOOSE values or simulated sampled measurand values are used
instead of original values since they are first received
LPHD
Data object
name
CDC
Semantics
Used in logical nodes…