CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-87
3
Table 3-88: Phase comparison negative sequence voltage (excluding FDH) data objects
Table 3-89: Phase comparison negative sequence voltage (for FDH) data objects
Table 3-90: Phase comparison advanced fault detector rate of change of positive sequence current (excluding FDH)
data objects
LNName: PhCmp1PTOV1
LDevice inst: Prot
UR element: Negative Sequence Voltage element (except FDH element
specifics) as a part of Phase comparison function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
87PC V2 FDL OP operand
R
general
BOOLEAN
ST 87PC V2 FDL OP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
BlkRef
γ
ORG
NEG SEQ VOL FD BLK setting of setting
group
γ
.
R
setSrcRef
ObjectReference SP NEG SEQ VOL FD BLK setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: PhCmp2PTOV1
LDevice inst: Prot
UR element: Negative Sequence Voltage element specific to FDH element
as a part of Phase comparison function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
87PC V2 FDH OP operand
R
general
BOOLEAN
ST 87PC V2 FDH OP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
LNName: PhCmp1FXOT1
LDevice inst: Prot
UR element: RATE OF CHANGE OF POS SEQ CURRENT element (except FDH
element specifics) as a part of Phase comparison function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
BlkRef
γ
ORG
POS SEQ di/dt BLK setting of setting
group
γ
.
R
setSrcRef
ObjectReference SP POS SEQ di/dt BLK setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
StrVal
ASG
POS SEQ di/dt FDL PICKUP setting
R
setMag
AnalogueValue SG
R
setMag.f
FLOAT32
POS SEQ di/dt FDL PICKUP
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1 is code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
minVal
AnalogueValue CF
R
minVal.f
FLOAT32
0.01
R
maxVal
AnalogueValue CF
R
maxVal.f
FLOAT32
5.00
R
stepSize
AnalogueValue CF
R
stepSize.f
FLOAT32
0.01
R
Op
ACT
87PC di1/dt FDL OP operand
R
general
BOOLEAN
ST 87PC di1/dt FDL OP
R