3-168
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-184: Field RTD data objects
3.5.4.12 Field units (FUnt)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-185: Field unit data objects
3.5.4.13 Field transducers (FTDRs)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-186: Field transducer data objects
LNName: FRTDsGGIO1
LDevice inst: System
UR element: Field RTDs (Resistance Temperature Detectors)
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Ind
Θ
SPS
RTD
Θ
Trouble On operand value
R
stVal
BOOLEAN
ST RTD
Θ
Trouble On
R
AnIn
Θ
MV
RTD
Θ
Temperature in degree Celsius
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
RTD
Θ
Temperature
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
23, the code for degree Celsius (°C)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF FRTDsGGIO1.AnIn
Θ
.db
R/W/C
zeroDb
INT32U
CF
0
R
LNName: FUnitGGIO1
LDevice inst: System
UR element: Field units
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Ind
Θ
SPS
U
Θ
On operand value
R
stVal
BOOLEAN
ST U
Θ
On
R
LNName: FTDRsGGIO1
LDevice inst: System
UR element: Field Transducers
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Ind
Θ
SPS
TDR
Θ
Trouble On operand value
R
stVal
BOOLEAN
ST TDR
Θ
Trouble On
R
AnIn
Θ
MV
TDR
Θ
Value
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
TDR
Θ
Value
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
db
INT32U
CF FTDRsGGIO1.AnIn
Θ
.db
R/W/C
zeroDb
INT32U
CF
0
R
DbMax
Θ
ASG
Maximum Value in deadband
calculations
R
setMag
AnalogueValue SP
R
setMag.f
FLOAT32
“Maximum Value” of TDR
Θ
R/C
minVal
AnalogueValue CF
R
minVal.f
FLOAT32
–9999.999
R
maxVal
AnalogueValue CF
R
maxVal.f
FLOAT32
9999.999
R