CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-153
3
Table 3-172: Breaker control data objects
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs
VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName
VISIBLE
STRING255
EX GEORG
R
InRef3
ORG
XCBR# INTERLOCK CLS setting.
R
GEORG
R
setSrcRef
ObjectReference SP XCBR# INTERLOCK CLS
reference to the data attribute to input
R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
XCBR# INTERLOCK CLS
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs
VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName
VISIBLE
STRING255
EX GEORG
R
LNName: Bkr0XCBR#
LDevice inst: System
UR element: Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Mod
INC
This logical node’s mode
R/Ctrl
stVal
ENUMERATED
ST
1 (on)
R
ctlModel
CtlModels
CF
0 (status only)
R
Health
INS
This logical node’s health
R
stVal
ENUMERATED
ST LPHD1.PhyHealth.stVal
R
EEHealth
ENS
Breaker health, value is 2 (yellow) when
breaker is out of service, 3 (red) when
breaker trouble is detected and breaker is
not out of service
R
INS
R
stVal
ENUMERATED
ST
2 when BREAKER # OOS is On, otherwise
3 when operand BREAKER # TROUBLE is
On, otherwise 1
R
Loc
SPS
Value of operand selected by setting
XCBR# ST.LOC OPERAND
R
stVal
BOOLEAN
ST
Value of operand selected by setting
XCBR# ST.LOC OPERAND
R
OpCnt
INS
Breaker operations counter.
R
stVal
INT32
ST
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1
R
units.multiplier
ENUMERATED
0
R
CBOpCap
INS
Mandatory data object which in this case
is fixed at 3
R
stVal
ENUMERATED
ST
3
R
OpOpn
ACT
BREAKER # OFF CMD (3-phase trip),
BREAKER # TRIP A, BREAKER # TRIP B and
BREAKER # TRIP C operands
R
general
BOOLEAN
ST BREAKER # OFF CMD
R
phsA
BOOLEAN
ST BREAKER # TRIP A
R
phsB
BOOLEAN
ST BREAKER # TRIP B
R
LNName: BkrCILO#
LDevice inst: System
UR element: Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C