CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE
2-45
2
"
2D80
Contact Output States, one per register (72
items)
0 to 1
---
1
F108
0 (Off)
"
2E00
Virtual Output States, one per register (120
items)
0 to 1
---
1
F108
0 (Off)
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2, 3, 4, or 6 Modules)
B30, C60, C70,
D30, D60, F35,
F60, G30, G60,
L30, L60, L90,
M60, T35, T60
2F00
Breaker 1 Arcing Acc Arcing Amp Phase A
0 to 99999999
kA2-cyc 1
F060
0
"
2F02
Breaker 1 Arcing Acc Arcing Amp Phase B
0 to 99999999
kA2-cyc 1
F060
0
"
2F04
Breaker 1 Arcing Acc Arcing Amp Phase C
0 to 99999999
kA2-cyc 1
F060
0
"
2F06
Breaker 1 Arcing Operating Time Phase A
0 to 65535
ms
1
F001
0
"
2F07
Breaker 1 Arcing Operating Time Phase B
0 to 65535
ms
1
F001
0
"
2F08
Breaker 1 Arcing Operating Time Phase C
0 to 65535
ms
1
F001
0
"
2F09
Breaker 1 Arcing Operating Time
0 to 65535
ms
1
F001
0
"
2F0A
Breaker 1 Arcing Amp Phase A
0 to 99999999
kA2-cyc 1
F060
0
"
2F0C
Breaker 1 Arcing Amp Phase B
0 to 99999999
kA2-cyc 1
F060
0
"
2F0E
Breaker 1 Arcing Amp Phase C
0 to 99999999
kA2-cyc 1
F060
0
"
2F10
Breaker 1 Arcing Amp Max Phase A
0 to 99999999
kA
1
F060
0
"
2F12
Breaker 1 Arcing Amp Max Phase B
0 to 99999999
kA
1
F060
0
"
2F14
Breaker 1 Arcing Amp Max Phase C
0 to 99999999
kA
1
F060
0
"
2F16
...Repeated for Breaker 2
B30, C60, C70,
F35, F60, L90,
T35, T60
2F2C
...Repeated for Breaker 3
B30, C60, F35,
F60, L90, T35,
T60
2F42
...Repeated for Breaker 4
B30, F35, T35,
T60
2F58
...Repeated for Breaker 5
"
2F6E
...Repeated for Breaker 6
Oscillography Values (Read Only)
All
3000
Oscillography Number of Triggers
0 to 65535
---
1
F001
0
"
3001
Oscillography Available Records
0 to 65535
---
1
F001
0
"
3002
Oscillography Last Cleared Date
0 to 400000000
---
1
F050
0
"
3004
Oscillography Number Of Cycles Per
Record
0 to 65535
---
1
F001
0
Oscillography Commands (Read/Write Command)
All
3005
Oscillography Force Trigger
0 to 1
---
1
F126
0 (No)
"
3011
Oscillography Clear Data
0 to 1
---
1
F126
0 (No)
Oscillography Analog Values (Read Only)
All
3012
Oscillography Number of Triggers
0 to 32767
---
1
F001
0
Fault Report Indexing (Read Only Non-Volatile)
C60, D30, D60,
F35, F60, L30,
L60, L90
3020
Number of Fault Reports
0 to 65535
---
1
F001
0
Fault Report Actual Values (Read Only Non-Volatile) (15 Modules)
C60, D30, D60,
F35, F60, L30,
L60, L90
3030
Fault Report 1 Time
0 to 4294967295
---
1
F050
0
"
3032
Fault Report 2 Time
0 to 4294967295
---
1
F050
0
Products
Address Register name
Range
Units
Step
Format
Default