3-50
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-35: Compensated overvoltage stage data objects
3.5.2.16 Continuous monitor (CnMntr)
This element is instantiated in the following products: L90.
Table 3-36: Continuous monitor data objects
3.5.2.17 Current (amp) unbalance (AmpUnb)
This element is instantiated in the following products: M60.
Table 3-37: Current unbalance data objects
LNName: CmpOvPTOV$
LDevice inst: Prot
UR element: Compensated Overvoltage stage $
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
COMP OV STG$ PKP operand
R
general
BOOLEAN
ST COMP OV STG$ PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
Op
ACT
COMP OV STG$ OP operand
R
general
BOOLEAN
ST COMP OV STG$ OP
R
Dpo
SPS
COMP OV STG$ DPO operand, which is
the inverse of COMP OV STG$ PKP
R
stVal
BOOLEAN
ST COMP OV STG$ DPO
R
LNName: CnMntrGAPC1
LDevice inst: Prot
UR element: Continuous Monitor element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
CONT MONITOR PKP operand
R
general
BOOLEAN
ST CONT MONITOR PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
CONT MONITOR OP operand
R
general
BOOLEAN
ST CONT MONITOR OP
R
InRef1
ORG
CONT MONITOR I-OP setting.
R
setSrcRef
ObjectReference SP CONT MONITOR I-OP setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef2
ORG
CONT MONITOR I-SUPV setting.
R
setSrcRef
ObjectReference SP Reference to the data object
selected by CONT MONITOR I-
SUPV
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef3
ORG
CONT MONITOR V-OP setting.
R
setSrcRef
ObjectReference SP Reference to the data object
selected by CONT MONITOR V-
OP
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef4
ORG
CONT MONITOR V-SUPV setting.
R
setSrcRef
ObjectReference SP Reference to the data object
selected by CONT MONITOR V-
SUPV
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: AmpUnbPTOC#
LDevice inst: Prot
UR element: Amp Unbalance element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
AMP UNBALANCE # PKP operand
R
general
BOOLEAN
ST AMP UNBALANCE # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown.
R