3-86
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-87: Phase comparison fault detector high (FDH) data objects
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
Str
ACD
87PC PKP operand
R
general
BOOLEAN
ST 87PC PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
Dpo
SPS
87PC DPO operand, which is the inverse
of 87PC PKP
R
stVal
BOOLEAN
ST 87PC DPO
R
Op
ACT
87PC OP operand
R
general
BOOLEAN
ST 87PC OP
R
FDLOp
SPS
87PC FDL OP operand
R
stVal
BOOLEAN
ST 87PC FDL OP
R
TransBlk
SPS
87PC TRANS BLOCK OP operand
R
stVal
BOOLEAN
ST 87PC TRANS BLOCK OP
R
RX
ζ
SPS
87PC RX
ζ
operand.
R
stVal
BOOLEAN
ST 87PC RX
ζ
R
CmpCt
β
I1
MV
CT# COMP I1 Mag in amperes
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
CT# COMP I1 Mag
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
5, the code for amperes
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF PhCmp1PDIF1.CmpCt#I1.db
R/W/C
zeroDb
INT32U
CF
0
R
CmpCt#I2
MV
CT# COMP I2 Mag in amperes
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
CT# COMP I2 Mag
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
5, the code for amperes
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF PhCmp1PDIF1.CmpCt#I2.
R/W/C
zeroDb
INT32U
CF
0
R
LNName: PhCmp2PDIF1
LDevice inst: Prot
UR element: 87PC SCHEME specific to FDH element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
InRef
γ
1
ORG
87PC FDH AUX setting of setting group
γ
. R
setSrcRef
ObjectReference SP 87PC FDH AUX setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef
γ
2
ORG
87PC FDH SUPV setting of setting group
γ
.
R
setSrcRef
ObjectReference SP 87PC FDH SUPV setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
Op
ACT
87PC FDH OP operand
R
general
BOOLEAN
ST 87PC FDH OP
R
LNName: PhCmp1PDIF1
LDevice inst: Prot
UR element: 87PC SCHEME (except FDH element specifics) and Charging
Current Compensation element
data obj. data attribute
Type
FC UR Name
Description
R/W/C