3-38
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.2 Accidental energization (AcdEnr)
This element is instantiated in the following products: G30, G60.
Table 3-19: Accidental energization data objects
3.5.2.3 Auxiliary overvoltage (AuxOv)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T60.
mag
AnalogueValue MX
R
mag.f
FLOAT32
0.0
R
Mod
ENC
Only instantiated in the Master logical
device
R/Ctrl
ctlVal
ENUMERATED
R
stVal
ENUMERATED
ST
R
ctlModel
CtlModels
CF LLN0.Mod.ctlModel
2, the code for SBO control with normal
security according to IEC 61850-7-2.
R/C
sboTimeout
INT32U
CF
30000
R
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF
0
R
GrRef
ORG
Reference to root logical device
R
setSrcRef
ObjectReference SP For communications, mapped to
Master ldName if not empty,
otherwise to the concatenation
of the IED name and “Master”.
For SCL, mapped to the
concatenation of the IED name
and “Master”.
reference to the data attribute to input
R
MltLev
SPG
Instantiated only in the Master logical
device
R
setVal
BOOLEAN
SP
R
<TT
Σ
DataS
et##>
DATA-SET
R
DSMemberRef[
η
] ObjectReference
DataSet Member
η
R/C
LNName: AcdEnrPIOC1
LDevice inst: Prot
UR element: Accidental Energization element – Over-current function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
ACCDNT ENRG OP operand
R
general
BOOLEAN
ST ACCDNT ENRG OP
R
Dpo
SPS
ACCDNT ENRG DPO operand
R
stVal
BOOLEAN
ST ACCDNT ENRG DPO
R
Armed
SPS
ACCDNT ENRG ARMED operand
R
stVal
BOOLEAN
ST ACCDNT ENRG ARMED
R
InRef
γ
ORG
ACCDNT ENRG OFFLINE setting for
setting group
γ
.
R
setSrcRef
ObjectReference SP ACCDNT ENRG OFFLINE
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
BlkRef
γ
ORG
ACCDNT ENRG BLOCK setting for setting
group
γ
.
R
setSrcRef
ObjectReference SP ACCDNT ENRG BLOCK
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: LLN0
LDevice inst: Prot
UR element: Nameplate information for the logical nodes
data obj. data attribute
Type
FC UR Name
Description
R/W/C