CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-143
3
units.SIUnit
ENUMERATED
33
R
units.multiplier
ENUMERATED
0
R
db
INT32U
CF SynChkRSYN#.DifHzClc.db
R/W/C
zeroDb
INT32U
CF
0
R
DifAngClc
MV
SYNCHROCHECK # DELTA PHASE, in
degrees
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
SYNCHROCHECK # DELTA PHASE
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
SYNCHROCHECK # DELTA PHASE
on deadband exception
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
9
R
units.multiplier
ENUMERATED
0
R
db
INT32U
CF SynChkRSYN#.DifAngClc.db
R/W/C
zeroDb
INT32U
CF
0
R
DifAngDis
MV
SYNCHROCHECK # SYNSCP D_PH, in
degrees
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
SYNCHROCHECK # SYNSCP
D_PH
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
SYNCHROCHECK # SYNSCP
D_PH on deadband exception
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
9
R
units.multiplier
ENUMERATED
0
R
db
INT32U
CF SynChkRSYN#.DifAngDis.db
R/W/C
zeroDb
INT32U
CF
0
R
V1Src
CMV
SYNCHROCHECK # V1 voltage phasor, in
primary volts
R
instCVal
Vector
MX
R
instCVal.mag.f
FLOAT32
SYNCHROCHECK # V1 MAG
R
instCVal.ang.f
FLOAT32
SYNCHROCHECK # V1 ANG
R
cVal
Vector
MX
R
cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
cVal.ang.f
FLOAT32
instCVal.ang.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29
R
units.multiplier
ENUMERATED
0
R
db
INT32U
CF SynChkRSYN#.V1Src.db
R/W/C
dbAng
INT32U
CF SynChkRSYN#.V1Src.dbAng
R/W/C
zeroDb
INT32U
CF
0
R
V2Src
CMV
SYNCHROCHECK # V2 voltage phasor, in
primary volts
R
instCVal
Vector
MX
R
instCVal.mag.f
FLOAT32
SYNCHROCHECK # V2 MAG
R
instCVal.ang.f
FLOAT32
SYNCHROCHECK # V2 ANG
R
cVal
Vector
MX
R
cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
cVal.ang.f
FLOAT32
instCVal.ang.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29
R
LNName: SynChkRSYN#
LDevice inst: Ctrl
UR element: Synchrocheck element # (ANSI 25)
data obj. data attribute
Type
FC UR Name
Description
R/W/C