3-214
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
DynArmd
SPS
This data object indicates that dynamic mode is armed.
The SYNC1 S-CLOSE ARMD operand, which becomes On when dynamic mode is
armed.
SynChkRSYN
DynDpo
SPS
The SYNC1 S-CLOSE DPO operand, which becomes Off when all criteria for
dynamic mode are fulfilled
SynChkRSYN
DynOp
SPS
This data object indicates that all criteria for dynamic mode are fulfilled if value is
TRUE else false.
The SYNC1 S-CLOSE OP operand, which becomes On when all criteria for dynamic
mode are fulfilled.
SynChkRSYN
Ena1
SPS
Function is Enabled.
The AR ENABLED operand.
Rec13pRREC, Rec3pRREC
EqLim
SPS
The number of pulses counted is equal to the set number.
Counter 1(CNT1) EQL operand, which indicates the number of pulses counted is
equal to the set number.
DigCntFCNT
EqpMismat
SPS
The configuration of modules does not match the stored order code.
The EQUIPMENT MISMATCH operand.
LPHD
EvtEna1
ENG
Setting to enable generation of events in event record, 0 = Disabled, 1 = Enabled GGIO3
EvtLED
SPS
An LED - Event Cause LED status. For graphical front panel.
The EVENT CAUSE LED 1 operand.
LEDsIHMI
EvtRcdClr
SPC
Clear Event Records (erase all Events).
The CLEAR EVENT RECORDS command.
Master/LLN0
Fail
SPS
Ground Protection Module Failure.
GPM-F (Field Ground Protection Module) Fail status.
The GPM-F FAILURE operand.
FldGnd0PHIZ
FDLOp
SPS
Overcurrent fault detector low has operated.
The 87PC FDL OP operand.
PhCmp1PDIF
FlexErrTkn
SPS
A FlexLogic equation is incorrect.
The FLEXLOGIC ERR TOKEN operand.
LPHD
Flt3Ph
SPS
Fault indication - Three phase fault.
The PHASE SELECT 3P operand.
PhSelGAPC
FltAB
SPS
Fault indication - Phase A to B.
The PHASE SELECT AB operand.
PhSelGAPC
FltABG
SPS
Fault indication - Phase A to B to ground.
The PHASE SELECT ABG operand.
PhSelGAPC
FltAG
SPS
Fault indication - Phase A to ground.
The PHASE SELECT AG operand.
PhSelGAPC
FltBC
SPS
Fault indication - Phase B to C.
The PHASE SELECT BC operand.
PhSelGAPC
FltBCG
SPS
Fault indication - Phase B to C to ground.
The PHASE SELECT BCG operand.
PhSelGAPC
FltBG
SPS
Fault indication - Phase B to ground.
The PHASE SELECT BG operand.
PhSelGAPC
FltCA
SPS
Fault indication - Phase C to A.
The PHASE SELECT CA operand.
PhSelGAPC
FltCAG
SPS
Fault indication - Phase C to A to ground.
The PHASE SELECT CAG operand.
PhSelGAPC
FltCG
SPS
Fault indication - Phase C to ground.
The PHASE SELECT CG operand.
PhSelGAPC
FltCntClr
SPC
TRUE = clear incipient fault count. The clear incipient fault counters command.
ICFltPTEF
FltCntPh
φ
INS
Number of detected incipient faults.
INCIPIENT FAULT 1 PH A/B/C FAULTS.
ICFltPTEF
FltLinID
VSS
Faulted line ID
FltRFLO
FltLocation
MV
Fault location in percentage.
The FAULT LOCATION in percentage of field winding from negative terminal in
case of single point injection. If double point injection, displays Invalid value.
FldGnd0PHIZ
FltLoopReact
MV
D30, D60, L60, L90 - The fault loop reactance
FltRFLO
Data object
name
CDC
Semantics
Used in logical nodes…