CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-65
3
phs
θ
CMV
R
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
I
θ
DIFF. CURRENT magnitude, in
primary amps
R
phs
θ
.instCVal.ang
.f
FLOAT32
I
θ
DIFF. CU
UR range -180...+180 converted to 0...360R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
I
θ
DIFF. CURRENT magnitude, in
primary amps, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
I
θ
DIFF. CU
UR range -180...+180 converted to 0...360R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit ENUMERATED
5, the code for amps
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF LinDfPDIF1.DifAClc.phs
θ
.db
R/W/C
phs
θ
.dbAng
INT32U
CF LinDfPDIF1.DifAClc.phs
θ
.dbAng
R/W/C
phs
θ
.zeroDb
INT32U
CF CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
R
neut
CMV
R
neut.instCVal
Vector
MX
R
neut.instCVal.mag
.f
FLOAT32
IG DIFF. CURRENT magnitude, in
primary amps
R
neut.instCVal.ang
.f
FLOAT32
IG DIFF. CU
UR range -180...+180 converted to 0...360R
neut.cVal
Vector
MX
R
neut.cVal.mag.f
FLOAT32
IG DIFF. CURRENT magnitude, in
primary amps, with deadband
R
neut.cVal.ang.f
FLOAT32
IG DIFF. CU
UR range -180...+180 converted to 0...360R
neut.units
Unit
CF
R
neut.units.SIUnit ENUMERATED
5, the code for amps
R
neut.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
neut.db
INT32U
CF LinDfPDIF1.DifAClc.neut.db
R/W/C
neut.dbAng
INT32U
CF LinDfPDIF1.DifAClc.neut.dbAng
R/W/C
neut.zeroDb
INT32U
CF CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
RstA
WYE
Restraint currents
R
phs
θ
CMV
R
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
I
θ
RESTR. CURRENT magnitude,
in primary amps
R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
I
θ
RESTR. CURRENT magnitude,
in primary amps, with deadband
R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit ENUMERATED
5, the code for amps
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF LinDfPDIF1.DifAClc.phs
θ
.db
R/W/C
phs
θ
.zeroDb
INT32U
CF CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
R
neut
CMV
R
neut.instCVal
Vector
MX
R
neut.instCVal.mag
.f
FLOAT32
IG RESTR. CURRENT magnitude,
in primary amps
R
neut.cVal
Vector
MX
R
LNName: LinDfPDIF1
LDevice inst: Prot
UR element: Line Differential element (ANSI 87L) phase and general
functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C