CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE
2-105
2
Phase Overvoltage (Read/Write Grouped Setting) (3 Modules)
B30, C60, C70,
D30, D60, F35,
F60, G30, G60,
L30, L60, L90,
M60, N60, T60
7040
Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7041
Phase Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
7042
Phase Overvoltage 1 Pickup
0.004 to 3
pu
0.001 F001
1000
"
7043
Phase Overvoltage 1 Delay
0 to 600
s
0.01
F001
100
"
7044
Phase Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
"
7045
Phase Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
"
7047
Phase Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7048
Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
7049
...Repeated for Phase Overvoltage 2
"
7052
...Repeated for Phase Overvoltage 3
Phase Distance (Read/Write Grouped Setting) (3 or 5 Modules)
D30, D60, G60,
L60, L90, T60
7070
Phase Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7071
Phase Distance Zone 1 Current Supervision 0.05 to 30
pu
0.001 F001
200
"
7072
Phase Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
"
7073
Phase Distance Zone 1 Direction
0 to 2
---
1
F154
0 (Forward)
"
7074
Phase Distance Zone 1 Comparator Limit
30 to 90
degrees 1
F001
90
"
7075
Phase Distance Zone 1 Delay
0 to 65.535
s
0.001 F001
0
"
7076
Phase Distance Zone 1 Block
0 to 4294967295
---
1
F300
0
"
7078
Phase Distance Zone 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7079
Phase Distance Zone 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
707A
Phase Distance Zone 1 Shape
0 to 1
---
1
F120
0 (Mho)
Fixed in G60
"
707B
Phase Distance Zone 1 RCA
30 to 90
degrees 1
F001
85
"
707C
Phase Distance Zone 1 DIR RCA
30 to 90
degrees 1
F001
85
"
707D
Phase Distance Zone 1 DIR Comp Limit
30 to 90
degrees 1
F001
90
"
707E
Phase Distance Zone 1 Quad Right Blinder 0.02 to 500
ohms
0.01
F001
1000
"
707F
Phase Distance Zone 1 Quad Right Blinder
RCA
60 to 90
degrees 1
F001
85
"
7080
Phase Distance Zone 1 Quad Left Blinder
0.02 to 500
ohms
0.01
F001
1000
"
7081
Phase Distance Zone 1 Quad Left Blinder
RCA
60 to 90
degrees 1
F001
85
"
7082
Phase Distance Zone 1 Volt Limit
0 to 5
pu
0.001 F001
0
"
7083
Phase Distance Zone 1 Transformer
Voltage Connection
0 to 12
---
1
F153
0 (None)
"
7084
Phase Distance Zone 1 Transformer
Current Connection
0 to 12
---
1
F153
0 (None)
"
7085
Phase Distance Zone 1 Rev Reach
0.02 to 500
ohms
0.01
F001
200
"
7086
Phase Distance Zone 1 Rev Reach RCA
30 to 90
degrees 1
F001
85
"
7087
Reserved (10 items)
---
---
---
F001
0
"
7091
...Repeated for Phase Distance Zone 2
"
70B2
...Repeated for Phase Distance Zone 3
D30, D60, L90
T60
70D3
...Repeated for Phase Distance Zone 4
"
70F4
...Repeated for Phase Distance Zone 5
Products
Address Register name
Range
Units
Step
Format
Default