UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-150: Fault report data file data objects
3.5.3.15 Frequency out-of-band accumulation (HzBnd)
This element is instantiated in the following products: G30, G60.
Table 3-151: Frequency out-of-band accumulation data objects
Table 3-152: Frequency out-of-band accumulation prefix instance number $ data objects
LNName: FltRFLO
ψψ
LDevice inst: CtrlUR element: Selected values from Fault Report Data f ile
ψψ
data obj. data attribute
Type
FC UR Name
Description
R/W/C
FltZ
CMV
Mandatory data attribute which in this
case is fixed at zero
R
cVal
Vector
MX
R
cVal.mag.f
FLOAT32
Fault impedance magnitude in
primary ohms calculated as
shown below
R
cVal.ang.f
FLOAT32
Fault impedance angle in
degrees calculated as shown
below
R
FltRis
MV
FAULT
ψψ
FAULT RESIST converted to
primary ohms
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
Actual Value FAULT
ψψ
FAULT
RESIST converted to primary
ohms
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
30, the code for primary electric
resistance in ohm (V/A)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
FltLoopRis
MV
FAULT
ψψ
LOOP RESIST converted to
primary ohms
R
mag
AnalogueValue MX
R
LNName: HzBndPTUF1
LDevice inst: Ctrl
UR element: Frequency OOB Accumulation element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
FREQ OOB ACCUM PKP operand, which is
indicates Op will operate when delay
expires.
R
general
BOOLEAN
ST FREQ OOB ACCUM PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown.
R
Op
ACT
FREQ OOB ACCUM OP operand
R
general
BOOLEAN
ST FREQ OOB ACCUM OP
R
BlkRef1
ORG
FREQ ACCUM BLOCK setting.
R
setSrcRef
ObjectReference SP FREQ ACCUM BLOCK.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: HzBnd$PTUF1
LDevice inst: Ctrl
UR element: Frequency OOB Accumulator $
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
FREQ OOB BAND $ PKP operand, which is
indicates Op will operate when delay
expires.
R
general
BOOLEAN
ST FREQ OOB BAND $ PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown.
R
Op
ACT
FREQ OOB BAND $ OP operand
R
general
BOOLEAN
ST FREQ OOB BAND $ OP
R
Dpo
SPS
FREQ OOB BAND $ DPO operand
R
stVal
BOOLEAN
ST FREQ OOB BAND $ DPO
R
HzObAccu
m
MV
FREQUENCY OOB BAND $
ACCUMULATION in percentage (%)
R