3-110
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.76 Trip bus (TrBus)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-125: Trip bus data objects
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
DIFF 5TH HARM I
θ
d magnitude,
in %
R
phs
θ
.instCVal.ang
.f
FLOAT32
DIFF 5TH HA
UR range -180...+180 converted to 0...360R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
DIFF 5TH HARM I
θ
d magnitude,
in %, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
DIFF 5TH HA
UR range -180...+180 converted to 0...360R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit ENUMERATED
1, the code for dimensionless
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF PctDifPDIF#.DifA5thH.phs
θ
.db
R/W/C
phs
θ
.dbAng
INT32U
CF PctDifPDIF#.DifA5thH.phs
θ
.dbAn
g
R/W/C
phs
θ
.zeroDb
INT32U
CF
0
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
RstA
WYE
Phase restraint currents
R
phs
θ
CMV
R
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
REST PHASOR I
θ
r magnitude, in
pu
R
phs
θ
.instCVal.ang
.f
FLOAT32
REST PHASOR
UR range -180...+180 converted to 0...360R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
REST PHASOR I
θ
r magnitude, in
pu, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
REST PHASOR
UR range -180...+180 converted to 0...360R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit ENUMERATED
1, the code for dimensionless
R
phs
θ
.units
.multiplier
ENUMERATED
-2, the code for a multiplier of Centi
R
phs
θ
.db
INT32U
CF PctDifPDIF#.RstA.phs
θ
.db
R/W/C
phs
θ
.dbAng
INT32U
CF PctDifPDIF#.RstA.phs
θ
.dbAng
R/W/C
phs
θ
.zeroDb
INT32U
CF
0
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
BlkRef
γ
ORG
PERCENT DIFF BLOCK for setting group
γ
. R
setSrcRef
ObjectReference SP PERCENT DIFF BLOCK for group
γ
.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: TrBusPTRC#
LDevice inst: Prot
UR element: Trip Bus element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
TRIP BUS # OP operand, which becomes
On when any input is On, and the element
is not blocked
R
general
BOOLEAN
ST TRIP BUS # OP
R
Str
ACD
TRIP BUS # PKP operand, which indicates
Op will operate when delay expires.
R
general
BOOLEAN
ST TRIP BUS # PKP
R
LNName: PctDifPDIF1
LDevice inst: Prot
UR element: Transformer Percent Differential function
data obj. data attribute
Type
FC UR Name
Description