3-58
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
instMag.f
FLOAT32
FIELD VOLTAGE
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29, the code for volts (W/A)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF FldGnd0PHIZ1.Vol.db
R/W/C
zeroDb
INT32U
CF
0
R
Amp
MV
FIELD CURRENT in amperes
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
FIELD CURRENT
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
5, the code for amperes
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF FldGnd0PHIZ1.Amp.db
R/W/C
zeroDb
INT32U
CF
0
R
InjVol
MV
INJECTED VOLTAGE in volts
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
INJECTED VOLTAGE
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29, the code for volts (W/A)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF FldGnd0PHIZ1.InjVol.db
R/W/C
zeroDb
INT32U
CF
0
R
FltLocation
MV
FAULT LOCATION in percentage of field
winding from negative terminal in case of
single point injection. If double point
injection, displays Invalid value
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
FAULT LOCATION
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
(percentage)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF FldGnd0PHIZ1.FltLocation.db
R/W/C
zeroDb
INT32U
CF
0
R
BlkRef
γ
ORG
FIELD GROUND BLK setting for setting
group
γ
.
R
setSrcRef
ObjectReference SP FIELD GROUND BLK for group
γ
. reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: FldGnd0PHIZ1
LDevice inst: Prot
UR element: FIELD GROUND INJ UC element functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C