CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE
2-151
2
"
A572
...Repeated for PID 4
Volts Per Hertz (Read/Write Grouped Setting) (2 Modules)
G30, G60, L90,
T60
A580
Volts Per Hertz 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
A581
Volts Per Hertz 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
A582
Volts Per Hertz 1 Pickup
0.8 to 4
pu
0.01
F001
80
"
A583
Volts Per Hertz 1 Curves
0 to 7
---
1
F240
0 (Definite
Time)
"
A584
Volts Per Hertz 1 TD Multiplier
0.05 to 600
---
0.01
F001
100
"
A585
Volts Per Hertz 1 Block
0 to 4294967295
---
1
F300
0
"
A587
Volts Per Hertz 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
A588
Volts Per Hertz 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
A589
Volts Per Hertz 1 T Reset
0 to 1000
s
0.1
F001
10
"
A58A
Volts Per Hertz 1 Voltage Mode
0 to 1
---
1
F186
0 (Phase-to-
Ground)
"
A58B
...Repeated for Volts Per Hertz 2
Volts Per Hertz Actual Values (Read Only) (2 Modules)
G30, G60, L90,
T60
A5A0
Volts Per Hertz 1
0 to 65.535
pu
0.001 F001
0
"
A5A1
Volts Per Hertz 2
0 to 65.535
pu
0.001 F001
0
FlexCurves C and D (Read/Write Setting)
All except C30
A600
FlexCurve C (120 items)
0 to 65535
ms
1
F011
0
"
A680
FlexCurve D (120 items)
0 to 65535
ms
1
F011
0
Annunciator (Read/Write Setting)
All
A700
Annunciator Alarm Input (96 items)
0 to 4294967295
---
1
F300
0
"
A7C0
Clear Latched Alarms
0 to 4294967295
---
1
F300
0
Annunciator Actual Values (Read Only)
All
A7D0
Annunciator Acknowledge or Reset Alarm
(3 items)
0 to 4294967295
---
1
F003
0
"
A7D6
Annunciator Input States (3 items)
0 to 4294967295
---
1
F003
0
"
A7DC
Annunciator Latched States (3 items)
0 to 4294967295
---
1
F003
0
"
A7E2
Annunciator Flashing States (3 items)
0 to 4294967295
---
1
F003
0
Pilot POTT (1P) (Read/Write Setting)
D60, L90
A800
POTT 1P Scheme Function
0 to 1
---
1
F102
0 (Disabled)
"
A801
POTT 1P Permissive Echo
0 to 2
---
1
F199
0 (Disabled)
"
A802
POTT 1P Rx Pickup Delay
0 to 65.535
s
0.001 F001
0
"
A803
POTT 1P Trans Block Pickup Delay
0 to 65.535
s
0.001 F001
20
"
A804
POTT 1P Trans Block Reset Delay
0 to 65.535
s
0.001 F001
90
"
A805
POTT 1P Echo Duration
0 to 65.535
s
0.001 F001
100
"
A806
POTT 1P Echo Lockout
0 to 65.535
s
0.001 F001
250
"
A807
POTT 1P Line End Open Pickup Delay
0 to 65.535
s
0.001 F001
50
"
A808
POTT 1P Seal In Delay
0 to 65.535
s
0.001 F001
0
"
A809
POTT 1P Ground Directional Overcurrent
Forward
0 to 4294967295
---
1
F300
0
"
A80B
POTT 1P Number of Communication Bits
0 to 2
---
1
F198
0 (1)
"
A80C
POTT 1P Rx1
0 to 4294967295
---
1
F300
0
"
A80E
POTT 1P Rx2
0 to 4294967295
---
1
F300
0
"
A810
POTT 1P Rx3
0 to 4294967295
---
1
F300
0
"
A812
POTT 1P Rx4
0 to 4294967295
---
1
F300
0
Products
Address Register name
Range
Units
Step
Format
Default