3-90
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-97: Phase comparison advanced fault detector negative sequence current (for FDH) data objects
Table 3-98: Phase comparison open breaker echo data objects
3.5.2.55 Phase current unbalance (PhAUn)
This element is instantiated in the following products: C70.
Table 3-99: Phase current unbalance data objects
LNName: PhCmp4PIOC1
LDevice inst: Prot
UR element: Negative Sequence Current element specific to FDH element
as a part of Phase comparison function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
SPS
87PC I_2 FDH OP operand
R
stVal
BOOLEAN
ST 87PC I_2 FDH OP
R
LNName: PhCmp5FXOT1
LDevice inst: Prot
UR element: OPEN BREAKER ECHO element as a part of Phase comparison
function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
InRef
γ
1
ORG
BRK 1 AUX CONTACT setting of setting
group
γ
.
R
setSrcRef
ObjectReference SP BRK 1 AUX CONTACT setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef
γ
2
ORG
BRK 1 CONT SUPV setting of setting group
γ
.
R
setSrcRef
ObjectReference SP BRK 1 CONT SUPV setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef
γ
3
ORG
BRK 2 AUX CONTACT setting of setting
group
γ
.
R
setSrcRef
ObjectReference SP BRK 2 AUX CONTACT setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef
γ
4
ORG
BRK 2 CONT SUPV setting of setting group
γ
.
R
setSrcRef
ObjectReference SP BRK 2 CONT SUPV setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef
γ
5
ORG
WEAK-INFEED KEYING setting of setting
group
γ
.
R
setSrcRef
ObjectReference SP WEAK-INFEED KEYING setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef
γ
6
ORG
WEAK-INFEED SUPV setting of setting
group
γ
.
R
setSrcRef
ObjectReference SP WEAK-INFEED SUPV setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
StrVal
ASG
Non-mapped mandatory DO, Non-
configurable read only value
R
setMag
AnalogueValue SG
R
setMag.f
FLOAT32
0
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
Op
ACT
87PC BKR ECHO PKP operand
R
general
BOOLEAN
ST 87PC BKR ECHO PKP
R
LNName: PhAUnPTOC#
LDevice inst: Prot
UR element: Phase Current Unbalance element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
CUR BAL # PKP operands (including
individual three phases), which indicates
Op will operate when delay expires.
R