CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE
2-161
2
"
B24C
...Repeated for Received Analog 31
"
B24E
...Repeated for Received Analog 32
IEC 61850 XSWI Configuration (Read/Write Setting) (24 Modules)
All except B90
B250
FlexLogic Operand for IEC 61850
XSWI.ST.Loc Status
0 to 4294967295
---
1
F300
0
"
B252
FlexLogic Operand for IEC 61850 XSWI
Open Interlock
0 to 4294967295
---
1
F300
1
"
B254
FlexLogic Operand for IEC 61850 XSW
Close Interlock
0 to 4294967295
---
1
F300
1
"
B257
...Repeated for Switch 2
"
B25E
...Repeated for Switch 3
"
B265
...Repeated for Switch 4
"
B26C
...Repeated for Switch 5
"
B273
...Repeated for Switch 6
"
B27A
...Repeated for Switch 7
"
B281
...Repeated for Switch 8
"
B288
...Repeated for Switch 9
"
B28F
...Repeated for Switch 10
"
B296
...Repeated for Switch 11
"
B29D
...Repeated for Switch 12
"
B2A4
...Repeated for Switch 13
"
B2AB
...Repeated for Switch 14
"
B2B2
...Repeated for Switch 15
"
B2B9
...Repeated for Switch 16
"
B2C0
...Repeated for Switch 17
"
B2C7
...Repeated for Switch 18
"
B2CE
...Repeated for Switch 19
"
B2D5
...Repeated for Switch 20
"
B2DC
...Repeated for Switch 21
"
B2E3
...Repeated for Switch 22
"
B2EA
...Repeated for Switch 23
"
B2F1
...Repeated for Switch 24
IEC 61850 XSWI Configuration (Read/Write Command) (24 Modules)
All except B90
B256
Command to Clear XSWI OpCnt (Operation
Counter)
0 to 1
---
1
F126
0 (No)
Wattmetric Ground Fault Settings (Read/Write Grouped) (2 or 4 Modules)
D30, D60, F35,
F60, L60, L90
B300
Wattmetric Ground Fault 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
B301
Wattmetric Ground Fault 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
B302
Wattmetric Ground Fault 1 Voltage
0 to 1
---
1
F234
0
(Calculated
VN)
"
B303
Wattmetric Ground Fault 1 Overvoltage
Pickup
0.02 to 3
pu
0.01
F001
20
"
B304
Wattmetric Ground Fault 1 Current
0 to 1
---
1
F235
0
(Calculated
IN)
"
B305
Wattmetric Ground Fault 1 Overcurrent
Pickup
0.002 to 30
pu
0.001 F001
60
"
B306
Wattmetric Ground Fault 1 Overcurrent
Pickup Delay
0 to 600
s
0.01
F001
20
Products
Address Register name
Range
Units
Step
Format
Default