3-198
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.6.7 Digital counters (DigCnt)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-209: Digital counter data objects
LNName: DigCntFCNT#
LDevice inst: Gen
UR element: Digital Counters #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
HiLim
SPS
Counter #(CNT#) HI, which indicates the
number of pulses counted is above the
set number.
R
stVal
BOOLEAN
ST Counter #(CNT#) HI
R
EqLim
SPS
Counter #(CNT#) EQL operand, which
indicates the number of pulses counted is
equal to the set number
R
stVal
BOOLEAN
ST Counter #(CNT#) EQL
R
LoLim
SPS
Counter #(CNT#) LO operand, which
indicates the number of pulses counted is
below the set number.
R
stVal
BOOLEAN
ST Counter #(CNT#) LO
R
CntVal
BCR
Counter # ACCUM, which indicates the
accumulated number of pulses
R
actVal
INT64
ST actual value of Counter #
ACCUM
R
frVal
INT64
ST actual value of Counter #
FROZEN (count)
R
frTm
TimeStamp
ST actual value of Counter #
FROZEN (date/time) combined
with Counter # MICROS
(fractional seconds)
R
units.SIUnit
ENUMERATED
COUNTER # UNITS
R
units.multiplier
ENUMERATED
COUNTER # UNITS
R
pulsQty
FLOAT32
CF
1
R
frEna
BOOLEAN
CF
R
strTm
TimeStamp
CF
0
R
frPd
INT32
CF
0
R
frRs
BOOLEAN
CF
R
InRef1
ORG
COUNTER # UP setting.
R
setSrcRef
ObjectReference SP COUNTER # UP setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef2
ORG
COUNTER # DOWN setting.
R
setSrcRef
ObjectReference SP COUNTER # DOWN setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef3
ORG
CNT# SET TO PRESET setting.
R
setSrcRef
ObjectReference SP CNT# SET TO PRESET setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef4
ORG
COUNTER # RESET setting.
R
setSrcRef
ObjectReference SP COUNTER # RESET setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef5
ORG
COUNTER # FREEZE/RESET setting.
R
setSrcRef
ObjectReference SP COUNTER # FREEZE/RESET
setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef6
ORG
COUNTER # FREEZE/COUNT setting.
R
setSrcRef
ObjectReference SP COUNTER # FREEZE/COUNT
setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
BlkRef1
ORG
COUNTER # BLOCK setting.
R
setSrcRef
ObjectReference SP COUNTER # BLOCK setting
reference to the data attribute to input
R/C