CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-199
3
3.5.6.8 Digital elements (DigEl)
This element is instantiated all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60).
Table 3-210: Digital element data objects
3.5.6.9 FlexElement element (FlxEl)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-211: FlexElement data objects
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: DigElGAPC#
LDevice inst: Gen
UR element: Digital Element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
Dig Element # PKP operand, which
indicates Op will operate when delay
expires.
R
general
BOOLEAN
ST Dig Element #(DE#) PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
Dig Element # OP operand, which
becomes On when the input is On, and
the element is not blocked
R
general
BOOLEAN
ST Dig Element #(DE#) OP
R
Dpo
SPS
Dig Element # DPO operand, which
indicates the element will drop out (Reset)
when delay expires.
R
stVal
BOOLEAN
ST Dig Element #(DE#) DPO
R
InRef1
ORG
DIG ELEM #INPUT setting.
R
setSrcRef
ObjectReference SP DIG ELEM #INPUT setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
BlkRef1
ORG
DIG ELEM # BLOCK setting.
R
setSrcRef
ObjectReference SP DIG ELEM # BLOCK.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: FlxElGAPC#
LDevice inst: Gen
UR element: FlexElement element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
FxE # PKP operand, which becomes On
when this element has picked up.
R
general
BOOLEAN
ST FxE # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
FxE # OP operand
R
general
BOOLEAN
ST FxE # OP
R
Dpo
SPS
FxE # DPO operand, which is the inverse
of FxE OP
R
stVal
BOOLEAN
ST FxE # DPO
R
OpSig
MV
FLEXELEMENT # OpSig, in per unit
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
FLEXELEMENT # OpSig
R
mag
AnalogueValue MX
R
mag.f
FLAOT32
FLEXELEMENT # OpSig on
deadband exception
R
units
Unit
CF
R
LNName: DigCntFCNT#
LDevice inst: Gen
UR element: Digital Counters #
data obj. data attribute
Type
FC UR Name
Description
R/W/C