CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-145
3
3.5.3.24 Thermal overload (ThmOvl)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, N60, T35,
T60.
Table 3-161: Thermal overload data objects
3.5.3.25 Three pole autoreclose (Rec3p)
This element is instantiated in the following products: D30, F35, F60, L30.
Table 3-162: Three pole autoreclose data objects
cdcNs
VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName
VISIBLE
STRING255
EX GEORG
R
InRef3
ORG
SYNCHK# SYNC CLOSE setting.
R
setSrcRef
ObjectReference SP SYNCHK# SYNC CLOSE.
reference to the data attribute to input
R/C
R
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
R
LNName: ThmOvlPTTR#
LDevice inst: Ctrl
UR element: THERMAL OVERLOAD PROTECTION # element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
THERMAL PROT # OP operand
R
general
BOOLEAN
ST THERMAL PROT # OP
R
Str
ACD
THERMAL PROT # PKP operand
R
general
BOOLEAN
ST THERMAL PROT # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown.
R
InRef2
ORG
THERMAL PROT # RESET setting.
R
setSrcRef
ObjectReference SP THERMAL PROT # RESET
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
BlkRef1
ORG
THERMAL PROT # BLOCK setting.
R
setSrcRef
ObjectReference SP THERMAL PROT # BLOCK.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: Rec3pRREC#
LDevice inst: Ctrl
UR element: Autoreclose element # functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
ShotCnt
INS
AUTORECLOSE# SHOT COUNT actual
value
R
stVal
INT32
ST AUTORECLOSE# SHOT COUNT
R
AutoRecSt
ENS
Autoreclosing status
R
stVal
ENUMERATED
ST
R
Ena1
SPS
AR# ENABLED operand
R
stVal
BOOLEAN
ST AR# ENABLED
R
ArRip
SPS
AR# RIP operand
R
stVal
BOOLEAN
ST AR# RIP
R
ArLO
SPS
AR# LO operand
R
stVal
BOOLEAN
ST AR# LO
R
ArBlk1
SPS
AR# BLK FROM MAN CLS operand
R
stVal
BOOLEAN
ST AR# BLK FROM MAN CLS
R
OpCls
ACT
AR# CLOSE operand
R
LNName: SynChkRSYN#
LDevice inst: Ctrl
UR element: Synchrocheck element # (ANSI 25)
data obj. data attribute
Type
FC UR Name
Description
R/W/C