Part Numbers
Part Numbers
Terminal Style
HR1S-ATE5110
Integrated Terminal Block
HR1S-ATE5110P
Removable Terminal Block
Dimensions (mm)
LED Indicator
Specifications
Applicable Standards
EN 60204-1: 2007, EN 60947-1: 2007
EN 60947-5-1:2004, EN 61000-6-2: 2005
EN 61000-6-4: 2007, EN 62061: 2005
EN ISO 13849-1: 2008, EN ISO 13849-2: 2008
Applicable Standards
for Use
EN 60204-1: 2006
EN ISO 13850: 2008
Performance Level (PL)
e (EN ISO 13849-1)
Safety Category
4 (EN ISO 13849-1)
Safety Integrity Level (SIL)
3 (EN 62061)
Stop Category
0, 1 (EN 60204-1) (Note)
Operating Temperature
–10 to +55ºC (no freezing)
Relative Humidity
30 to 85% RH (no condensation)
Impulse Withstand Voltage
4 kV (IEC 60947-5-1)
Shock Resistance
150 m/s2, 11m sec, 3 shocks in each 3 axes
Vibration Resistance
10 to 60 Hz, amplitude 0.35 mm
60 to 150 Hz, acceleration 50 m/s2
Degree of Protection
Terminal: IP20 Enclosure: IP40
Rated Voltage
24V AC –20% +10%
24V DC –20% +20%
Power Consumption
24V AC: 8 VA max. 24V DC: 4W max.
Overcurrent Protection
Built-in, electronic
Minimal Applicable Load
17V DC / 10 mA (initial value)
Response Time
ON to OFF: 20 ms max. (instantaneous output)
Overvoltage Category
III
Pollution Degree
2
Rated Insulation Voltage
300V AC
Safety Outputs
Instantaneous (Stop Cat 0)
2NO
Time-delay (Stop Cat 1)
3NO
Monitor Contacts
4NO (PNP)
Output Contact
Ratings
Safety
Circuit
AC15
C300 (230V AC / Ie=0.75A)
DC13
24V DC / Ie=1A
Time-
delay
Circuit
AC15
C300 (230V AC/ Ie=0.75A)
DC13
24V DC / Ie=1A
Preset Time
0, 0.5, 1, 2, 4, 6, 8, 10, 15, 20, 25, 30 sec.
Auxiliary Circuit
24V DC / 20 mA (PNP)
Mechanical Durability
10,000,000 operations
Electrical Life
See Output Contact Electrical Life graph (last page)
Rated Current
Total output: 8A max. 1 output 4A max.
Wire Size
HR1S-ATE5110
Single wire: 0.2 to 2.5 mm2 max. (24~14 AWG)
Multiple wires: 0.14 to 0.75 mm2 max.
HR1S-ATE5110P
Single wire: 0.2 to 2.5 mm2 max.(24~14 AWG)
Multiple wires: 0.2 to 1.5 mm2 max.
Weight (approx.)
280g
Note: Safety output contact
Stop category 0
Time-delay output contact
Stop category 1
Use a 4A fuse (Type gG) for power protection. Use a 6A fuse (Type gG) for safety output
•
protection. Use a 4A fuse (Type gG) for time-delay output and auxiliary output protection.
HR1S-ATE5110 Integrated Terminal Type
HR1S-ATE5110P Removable Terminal Type
EN ISO 13849-1 Performance Level e, Safety Category 4
•
compliant, and EN 62061 Safety Integrity Level 3.
Integrated and removable teminal styles available.
•
Compact design: 45 mm in width.
•
Time delay outputs: 3NO
•
Auxiliary outputs enable monitoring of power, safety inputs, and a time
•
delay output
Environmentally friendly, RoHs directive compliant.
•
UL Listed, CSA certified, TÜV NORD approved.
•
A1/A2
Fuse
Input A
S12
Input B
S22
Stop 1
A1/A2 Fuse: Turns on when power circuit is normal.
•
Input A S12: Turns on when S11–S12 is closed.
•
Input B S22: Turns on when S21–S22 is closed.
•
Stop1:
Turns on when the time-delay output
•
circuits 57-58, 67-68, and 77-78 are closed.
Safety Control Relay HR1S-ATE