![Fuji Electric ALPHA7 User Manual Download Page 623](http://html1.mh-extra.com/html/fuji-electric/alpha7/alpha7_user-manual_2341766623.webp)
CHAPTER 15 STANDARDS COMPLIANCE
15-10
Complying with "Guideline for Suppressing Harmonics by Customers Receiving High Voltage
or Special High Voltage"
15
(1) Regulation scope
Generally speaking, regulations apply if the following two conditions are satisfied.
The device is receiving high or extra-high voltage.
Converter load "equivalent capacity" exceeds the standard value (50kVA when receiving 6.6 kV)
for the receiving voltage.
If calculating "equivalent capacity" in accordance with the guidelines, a supplementary description
is provided in "15.4.2.1 Equivalent Capacity Calculation".
(2) Regulation method
Regulate the size (calculated value) of the harmonic current flowing from the customer's power
receipt point to the system. Regulation values are proportional to contracted demand. Guideline
regulation values are shown in Table 15.4-1.
If calculating "harmonic current" in accordance with the guidelines, a supplementary description is
provided in "15.4.2
Complying with "Guideline for Suppressing Harmonics by Customers
Receiving High Voltage or Special High Voltage".
Table 15.4-1 Harmonic outflow current upper limit per 1kW of contracted demand (mA/kW)
Receiving
voltage
5th
7th
11th
13th
17th
19th
23rd
25th and
above
6.6 kV
3.5
2.5
1.6
1.3
1.0
0.90
0.76
0.70
22 kV
1.8
1.3
0.82
0.69
0.53
0.47
0.39
0.36
15.4.2 Complying with "Guideline for Suppressing Harmonics by
Customers Receiving High Voltage or Special High Voltage"
If performing calculations for "servo amplifiers" in accordance with the guidelines, do so as follows.
15.4.2.1 Equivalent Capacity Calculation
Equivalent capacity is calculated by multiplying the (input rated capacity) by (conversion factor),
however, the input rated capacity value is not indicated in servo amplifier catalogs, and is therefore
described below.
(1) Servo amplifier rated capacity equivalent to Pi
In the guidelines, a 6-pulse converter is used as a reference for conversion factor 1, and
therefore it is necessary to express the servo amplifier input rated capacity as a value including
the harmonic current equivalent to conversion factor 1.
To be more specific, input fundamental harmonic current I1 is calculated as follows from the kW
rating and efficiency of the motor (load) and efficiency of the servo amplifier:
Summary of Contents for ALPHA7
Page 1: ......
Page 3: ...ii...
Page 22: ...0 1 CHAPTER 0 INTRODUCTION 0...
Page 36: ...1 1 CHAPTER 1 INSTALLATION 1...
Page 47: ...CHAPTER 1 INSTALLATION 1 12 Servo Amplifier 1...
Page 48: ...2 1 CHAPTER 2 WIRING 2...
Page 163: ...CHAPTER 2 WIRING 2 116 Safety Function 2...
Page 164: ...3 1 CHAPTER 3 OPERATION 3...
Page 192: ...4 1 CHAPTER 4 PARAMETER 4...
Page 317: ...CHAPTER 4 PARAMETER 4 126 Extension Function 2 Setting Parameters 4...
Page 318: ...5 1 CHAPTER 5 SERVO ADJUSTMENT 5...
Page 353: ...CHAPTER 5 SERVO ADJUSTMENT 5 36 Special Adjustment Vibration Suppression 5...
Page 354: ...6 1 CHAPTER 6 KEYPAD 6...
Page 408: ...7 1 CHAPTER 7 MAINTENANCE AND INSPECTION 7...
Page 434: ...8 1 CHAPTER 8 SPECIFICATIONS 8...
Page 460: ...9 1 CHAPTER 9 CHARACTERISTICS 9...
Page 472: ...10 1 CHAPTER 10 PERIPHERAL EQUIPMENT 10...
Page 516: ...11 1 CHAPTER 11 ABSOLUTE POSITION SYSTEM 11...
Page 523: ...CHAPTER 11 ABSOLUTE POSITION SYSTEM 11 8 Calculation of Battery Life 11...
Page 524: ...12 1 CHAPTER 12 POSITIONING DATA 12...
Page 540: ...13 1 CHAPTER 13 MODBUS RTU COMMUNICATION 13...
Page 579: ...CHAPTER 13 MODBUS RTU COMMUNICATION 13 40 Communications Procedures 13...
Page 580: ...14 1 CHAPTER 14 PC LOADER 14...
Page 614: ...STANDARDS COMPLIANCE CHAPTER 15 15...
Page 628: ...CHAPTER 16 APPENDIXES 16...
Page 661: ...CHAPTER 16 APPENDIXES 34 Product Warranty 16 16 7 Product Warranty...
Page 662: ......