CHAPTER 2 WIRING
2-110
Safety Function
2
2.7 Safety Function
2.7.1 Overview
With the ALPHA7 Series, the servo amplifier output transistor is stopped by hardware circuit, and the
motor is slowly stopped (free-run stop) by opening (turning OFF) safety device connection connector
CN6 [EN1+] and [EN2+] inputs. This is the Cat.0 (uncontrolled stoppage) safety stop function (STO)
regulated by EN60204-1, and complies with functional safety standards.
If constructing a safety system, a safety shutoff device was required outside the servo amplifier,
however, this is no longer required by using the safety stop function (STO).
Table 2.7.1-1 Functional safety performance
EN ISO 13849-1: 2015
Category
3
Performance level
e
Average diagnostic coverage
90% or higher (DCave medium)
Response time / Fault reaction time
50 ms or less (response time)
Mean time to dangerous failure for each
channel
62 years or longer (MTTFd)
EN 61508-1 to -7
EN 61800-5-2
Safety function
Output torque OFF function (STO)
Safety level
SIL3
Hardware fault tolerance
1 (HFT)
Safe failure fraction
90% or higher (SFF)
Probability of failure per hour
Less than 1.5 x 10
-8
(PFH)
Probability of failure on demand average [h
-1
]
Less than 1.5 x 10
-4
(PFDavg)
Proof test interval
10 years
WARNING
The servo amplifier output cutoff function uses the safety stop function (STO) regulated by
IEC61800-5-2, however, this is not designed to completely cut off the power supply and motor
electrically. Consequently, depending on the servo system application, it will be necessary to
employ such mechanisms as a brake for mechanical locking, or motor terminal protection to prevent
electric shock in order to ensure the safety of end users.
The servo amplifier output cutoff function does not completely cut off the power supply and motor
electrically, and therefore the servo amplifier power supply should be completely cut off, and wiring
and maintenance work carried out after 5 minutes or longer have elapsed.
Voltage occurs at the servomotor terminals during free-run triggered by the output cutoff function,
and therefore maintenance, inspection, and wiring work should be carried out after ensuring that the
servomotor has come to a complete stop.
Failure to observe this could result in electric shock.
Summary of Contents for ALPHA7
Page 1: ......
Page 3: ...ii...
Page 22: ...0 1 CHAPTER 0 INTRODUCTION 0...
Page 36: ...1 1 CHAPTER 1 INSTALLATION 1...
Page 47: ...CHAPTER 1 INSTALLATION 1 12 Servo Amplifier 1...
Page 48: ...2 1 CHAPTER 2 WIRING 2...
Page 163: ...CHAPTER 2 WIRING 2 116 Safety Function 2...
Page 164: ...3 1 CHAPTER 3 OPERATION 3...
Page 192: ...4 1 CHAPTER 4 PARAMETER 4...
Page 317: ...CHAPTER 4 PARAMETER 4 126 Extension Function 2 Setting Parameters 4...
Page 318: ...5 1 CHAPTER 5 SERVO ADJUSTMENT 5...
Page 353: ...CHAPTER 5 SERVO ADJUSTMENT 5 36 Special Adjustment Vibration Suppression 5...
Page 354: ...6 1 CHAPTER 6 KEYPAD 6...
Page 408: ...7 1 CHAPTER 7 MAINTENANCE AND INSPECTION 7...
Page 434: ...8 1 CHAPTER 8 SPECIFICATIONS 8...
Page 460: ...9 1 CHAPTER 9 CHARACTERISTICS 9...
Page 472: ...10 1 CHAPTER 10 PERIPHERAL EQUIPMENT 10...
Page 516: ...11 1 CHAPTER 11 ABSOLUTE POSITION SYSTEM 11...
Page 523: ...CHAPTER 11 ABSOLUTE POSITION SYSTEM 11 8 Calculation of Battery Life 11...
Page 524: ...12 1 CHAPTER 12 POSITIONING DATA 12...
Page 540: ...13 1 CHAPTER 13 MODBUS RTU COMMUNICATION 13...
Page 579: ...CHAPTER 13 MODBUS RTU COMMUNICATION 13 40 Communications Procedures 13...
Page 580: ...14 1 CHAPTER 14 PC LOADER 14...
Page 614: ...STANDARDS COMPLIANCE CHAPTER 15 15...
Page 628: ...CHAPTER 16 APPENDIXES 16...
Page 661: ...CHAPTER 16 APPENDIXES 34 Product Warranty 16 16 7 Product Warranty...
Page 662: ......