CHAPTER 4 PARAMETER
4-90
Extended Function Setting Parameters
4
PA2_66 Flying start at speed control
No.
Name
Setting range
Default
value
Change
66
Flying start at speed
control
0: No flying start
1: Flying start
0
Power
The parameter is enabled under speed control.
If servo-on is turned on during free-run operation, the speed at the timing is picked and acceleration
begins at the speed.
If the control power of the servo amplifier is turned off, the dynamic brake is applied, causing sudden
stop.
The speed at the timing of control power-on is not picked in this case.
PA2_67 Alarm detection at undervoltage
No.
Name
Setting range
Default
value
Change
67
Alarm detection at
undervoltage
0: No detection
1: Detection
1
Power
Select whether or not to detect alarms when undervoltage is detected.
The detected alarms include control power undervoltage and main power undervoltage.
PA2_68 Main power shutoff detection time
No.
Name
Setting range
Default
value
Change
68
Main power shutoff
detection time
35 [ms] to 1000 [ms]
35
Power
Specify the time for detecting shutoff of the main power. Power supply phases to be detected are L1
and L2.
The AC power is detected.
If power is restored after the time specified in this parameter since the main power is turned off with
servo-on turned on, a main circuit power undervoltage alarm (LVP) is caused.
Avoid repeating turning on or off frequently in a short time.
However, if power is restored after the time specified in this parameter and 1 [s], no alarm is detected.
To supply DC power, set at 1000 [ms]. If this is the case, the detection function is canceled.
To supply AC power, leave the default value unchanged in regular cases.
Summary of Contents for ALPHA7
Page 1: ......
Page 3: ...ii...
Page 22: ...0 1 CHAPTER 0 INTRODUCTION 0...
Page 36: ...1 1 CHAPTER 1 INSTALLATION 1...
Page 47: ...CHAPTER 1 INSTALLATION 1 12 Servo Amplifier 1...
Page 48: ...2 1 CHAPTER 2 WIRING 2...
Page 163: ...CHAPTER 2 WIRING 2 116 Safety Function 2...
Page 164: ...3 1 CHAPTER 3 OPERATION 3...
Page 192: ...4 1 CHAPTER 4 PARAMETER 4...
Page 317: ...CHAPTER 4 PARAMETER 4 126 Extension Function 2 Setting Parameters 4...
Page 318: ...5 1 CHAPTER 5 SERVO ADJUSTMENT 5...
Page 353: ...CHAPTER 5 SERVO ADJUSTMENT 5 36 Special Adjustment Vibration Suppression 5...
Page 354: ...6 1 CHAPTER 6 KEYPAD 6...
Page 408: ...7 1 CHAPTER 7 MAINTENANCE AND INSPECTION 7...
Page 434: ...8 1 CHAPTER 8 SPECIFICATIONS 8...
Page 460: ...9 1 CHAPTER 9 CHARACTERISTICS 9...
Page 472: ...10 1 CHAPTER 10 PERIPHERAL EQUIPMENT 10...
Page 516: ...11 1 CHAPTER 11 ABSOLUTE POSITION SYSTEM 11...
Page 523: ...CHAPTER 11 ABSOLUTE POSITION SYSTEM 11 8 Calculation of Battery Life 11...
Page 524: ...12 1 CHAPTER 12 POSITIONING DATA 12...
Page 540: ...13 1 CHAPTER 13 MODBUS RTU COMMUNICATION 13...
Page 579: ...CHAPTER 13 MODBUS RTU COMMUNICATION 13 40 Communications Procedures 13...
Page 580: ...14 1 CHAPTER 14 PC LOADER 14...
Page 614: ...STANDARDS COMPLIANCE CHAPTER 15 15...
Page 628: ...CHAPTER 16 APPENDIXES 16...
Page 661: ...CHAPTER 16 APPENDIXES 34 Product Warranty 16 16 7 Product Warranty...
Page 662: ......