
48
5. Setting Parameters
SD3 Series Instruction Manual
5. Parameters
No. 80.0
Position command filter 1:
Smoothing 1 - Moving average counter
Range
Default
Characteristics
1 to 6,250
(See below)
[ - ]
No. 81.0
Position command filter 4:
Smoothing 2 - Moving average counter
1 to 1,250
Function
Use
These items are used to smooth the speed changes in high deceleration/
acceleration, and can be used to suppress vibrations at settling time as well.
Use Filter 4 (Smoothing Filter 2) first.
To increase the smoothing effect further, use Filter 1 (Smoothing filter 1).
A larger value makes acceleration and deceleration smoother, but the response will become slower.
See the table below for the delay time calculation formula.
Filter 4 (Smoothing Filter 2) suppress the vibrations caused by the Gain FF compensation 2.
Motor Capacity Delay time Calculation Formula
50 W to 750 W:
0.16 ms
× Moving average count = Delay time
1 kW to 2 kW :
0.2 ms
■ Setup of Vibration Suppression
Positioning will take longer as much as the delay time specified above. Set this item within the range
acceptable to the equipment.
① Check the vibration interval in waveforms of position deviation and torque command at settling time.
② Calculate the moving average count as described below.
③ Using Filter 4 may reduce the resonant vibrations.
④ If suppression of the vibrations is not effective enough, recalculate the moving average count based
on the vibration interval, and set it to Filter 1.
Motor Capacity Moving average count and Vibration interval to compress
50 W to 750 W:
6,250
× Vibration interval [s] = Moving average count
1 kW to 2 kW :
5,000
■ Default
Motor Capacity
Filter 1 (No.80.0)
Filter 4 (No.81.0)
50 W to 750 W
25
10
1 kW to 2 kW
20
10
The default value of Position command filter 1: Type (No.66.0) is 0 (no filter).
Prerequisite
Position command filter 1: Selection (No.66.0) = 1 (Smoothing filter 1)
Position command filter 4: Selection (No.66.1) = 1 (Enable)
Remark
Before setting this parameter, wait at least 3 secs after the motor stops. In addition, configure it
where the command pulse is not being input.
Setting this parameter during pulse input or presence of residual pulse could cause positioning failure.
The larger the setting is, the longer the delay time from command input becomes.
Related To
No.66.0, No.66.1
7
Tuning
Summary of Contents for SD3 Series
Page 1: ...R FATEK AUTOMATION CORP Instruction Manual AC SERVO MOTOR and SERVO AMPLIFIER SD3 Series...
Page 6: ...6 MEMO SD3 Series Instruction Manual...
Page 52: ...32 MEMO 2 Specifications SD3 Series Instruction Manual...
Page 92: ...40 MEMO 3 Preparation SD3 Series Instruction Manual...
Page 292: ...48 MEMO SD3 Series Instruction Manual 6 Operation...
Page 338: ...46 MEMO SD3 Series Instruction Manual 7 Tuning...
Page 362: ...24 MEMO 8 Troubleshooting SD3 Series Instruction Manual...
Page 395: ...MEMO SD3 Series Instruction Manual...
Page 396: ...R...