Functions
MFC
4.
4.8
Alarms
The alarms are output via relay contacts and the red LED. The
number of up to eight alarms is stipulated in the application.
Each alarm can be assigned the following functions:
•
Limit value = Min
All measured values individually
selectable Cl
2
, pH, mV, Cl-N,
conductivity, etc.
•
Limit value = Max
All measured values individually
selectable Cl
2
, pH, mV, Cl-N,
conductivity, etc.
•
Digital inputs
1 to 3 can be selected individually
•
Error
The type of alarm can be selected in the "Alarms" menu in the
displays "Alarm ... Functions" (display 1.6.1 and 1.6.2“Alarm -
Menu 1.6" on page 139) There are three types of alarm.
In all alarm types the response can be influenced by entering a
delay (td) (refer to the diagrams in this chapter).
Unlatched alarm without
acknowledgement option (N.O.
unlatched N.C. unlatched)
The LED lights up in the event of an alarm and goes out
automatically when the alarm conditions are eliminated. The same
applies for the contact.
M I N
R e l a y w i t h o u t
d e l a y
L E D w i t h o u t
d e l a y
R e l a y w i t h
d e l a y
L E D w i t h
d e l a y
R e l a y w i t h
d e l a y
L E D w i t h
d e l a y
A l a r m ( u n l a t c h e d )
t
d
t
d
t
d
t
d
t
d
t
d
t
d
t
d
t
d
t
d
t
d
t
d
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...