130
WT.050.580.000.DE.IM.0714
Operation
MFC
5.
selectable for 3 electrode cells)
Adjustment of the reference temperature for the conductivity
measurement:
20°C / 25°C
Quant. salinity
=> NaCl in g/l / NaCl in % / TDS in g/l / off
TDS factor
=> 0.4 ... 1.0 (with active TDS display)
TDS:
Total Dissolved Solids = filtrate dried solid matter content in g/l.
The TDS factor depends on the composition of the sample water
and must determined for each water type.
Press the softkey
to show additional setting menus in the
measuring range menu.
CAN segment MW -> 01 (01...31) (--off)
Setting the CAN segment in which the measured value is to be
transmitted.
CAN addr. MW -> -- (00...31) (--off)
Setting the CAN address to which the measured value is to be
transmitted.
Limit value 1
Min
within measuring range
Max
within measuring range
Hysteresis
Depends on measuring range
0.01 to 0.25 / 00.1 to 05.0 / 1 to 50
Limit value 2
Min Yout/Ym
0–100.0 % (not in single feedback
closed-loop control)
Max Yout/Ym
0–100.0 % (not in single feedback
closed-loop control)
Ym is only output if the
actuator feedback is present,
otherwise the controller output is Yout
Hysteresis
0.1 to 5.0 %
Min Ypi
0–100.0 % (for compound-loop-
controller only)
Max Ypi
0–100.0 % (for compound-loop
controller only)
Hysteresis
0.1 to 5.0 % (for compound-loop-
controller only)
Adaption
Adaption is only available for single feed back control with "DES"
modules.
Tu
1–3600 s (60 s)
Ts
0.1 to 480.0 min (10 min)
Reference temp.
LF
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...