MFC
Description
3.
15
Relay plug-in card
8x Relay outputs (two-way switch)
•
Switching values
5 A, 250 V AC, 1250 VA max
5 A, 220 V DC, 150 W max
•
UL/CSA-rating
5 A, 1/6 HP 125, 250 V AC
5 A, 30 V DC, 30 W max
1 A, 30 V DC – 0.24 A, 125 V DC
Storage temperature:
-20 to +70 °C
Analog outputs plug-in card
4x Outputs (freely configurable)
•
Output 0/4–20 mA
•
Accuracy < 0.5 % FS
•
Load max. can be switched over 1000 Ohm / 400 Ohm
•
Temperature drift max. 0.2 % / 10 °C
•
Load monitoring
•
Electrically isolated up to 50 V to ground
Storage temperature:
-20 to +70 °C
Calibration:
pre-calibrated
Please note
All sensor measuring modules are electrically isolated to 50 V to
ground.
DES measuring module
3 electrode cell
Sensor:
3 electrode cell
Principle of operation:
Potentiostatic amperometry
Temperature drift
max. 0.2 % / 10 K
Linearity error:
< 0.1 %
Calibration:
pre-calibrated
Upot cell voltage:
0 to +1000 mV
Upot accuracy:
± 20 mV
Upot temperature drift
0.5 % / 10 K
Cell current:
-7 to 1000 µA
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...