6.
Please note
Cable extension:
The sensor cable for chlorine, conductivity and total chlorine may
be extended to a max. of 50 m.
If the pH, Redox or fluoride sensor cables must be extended (max.
50 m), an impedance converter must be attached to the sensor.
The impedance converter converts the very high-resistance
sensor signal into a low-resistance signal. The impedance
converter is supplied by an installed battery. The life of the battery
is approx. 5 years; the impedance converter should be sent to
Evoqua Water Technologies GmbH Günzburg for battery
replacement.
Arrangement of
the plug-in cards and cables
A mA-out plug-in card
B mA/V input - module 5 plug-in card
C Module 4 plug-in card
D Module 3 plug-in card
E Module 2 plug-in card
F
Module 1 plug-in card
G Relay card
H Terminal strip
Please note
Should you wish to retrofit additional sensor measuring modules,
information is provided in the packaging of the additionally ordered
sensor measuring modules and in the included retrofitting manual.
Depending on the application, various controller functions are
available for slot 1 and 2 (module 1 and module 2) (see 4.4
A B C D E F
G H
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...