MFC
Description
3.
19
3.1.3
Flow block assembly VariaSens
Housing
Dimensions (W x H x D):
215 x 375 x 155 mm
Weight:
approx. 1.5 kg
Connections
Sample water:
PVC hose 6 x 3 mm or
PE hose 6 x 1 mm
Thread connection:
G1/2" or NPT-1/4“
Flow control valve
Flow rate:
approx. 33 l/h (controlled)
Control range:
0.2 to 4.0 bar
Back-pressure:
- non-pressurised version
(open drain)
- pressurised version 1.5 bar
Sample water temperature
max. +50 °C
Multi sensor
Switching point:
21 l/h ± 3 l/h
Switching hysteresis:
2 l/h
Temperature sensor:
Pt 1000
3.1.4
Y flow-through adapter
Y flow-through adapter pH/mV
Back-pressure:
non-pressurised/pressurised
Version (max. 6 bar)
Sample water temperature:
max +50 °C
Y flow-through adapter fluoride
Back-pressure:
non-pressurised version
Sample water temperature:
max +50 °C
Y flow-through adapter
conductivity
Back-pressure
pressurised version up to 6 bar
Sample water temperature:
max +50 °C
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...