MFC
Installation
6.
201
the set 0 % position and the 100 % position.
8
Check the position in a second operation:
Select the "MANUAL" operating mode.
Move to various positions via the MAN.DOS key and check
dosing rate.
Repeat calibration at 0 % and 100 %, if necessary.
9
Determine the running time of the positioner from 0 % to
100 %.
10
Enter the determined running time in the "Cl
2
Dosing" window
under Ty.