20
WT.050.580.000.DE.IM.0714
Description
MFC
3.
3.1.5
Electrodes and sensors
pH electrode
Max. measuring range:
pH 0–12
Operating temperature range:
-5 to +80 °C
Storage temperature range:
-5 to +30 °C
Sample water conductivity:
200 µS/cm – 200 mS/cm
Max. operating pressure:
6 bar
Redox electrode
Max. measuring range:
-1000 to +1000 mV
Operating temperature range:
-10 to +80 °C
Storage temperature range:
-5 to +30 °C
Sample water conductivity:
200 µS/cm – 200 mS/cm
Max. operating pressure:
6 bar
Fluoride electrode
Max. measuring range:
0.2 to 20 mg/l
Operating temperature range:
0 to +80 °C
Storage temperature range:
-5 to +30 °C
Sample water conductivity:
200 µS/cm – 200 mS/cm
Max. operating pressure:
non-pressurised
Conductivity electrode
Measuring system:
4 electrode system LF325
Principle of operation:
4 conductor measurement
Operating temperature range:
-5 to +100 °C
Storage temperature range:
-5 to +50 °C
Cell constant:
0.48 cm
-1
± 1.5 %
Max. operating pressure:
10 bar
Measuring ranges:
0.100 mS/cm to 200 mS/cm
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...