Example 2:
An MFC-Cl
2
++ (master or slave) is installed with an MFC pH in
order to compensate the chlorine measurement with the pH value.
In this application, both units need not be operated in the same
segment. In the following example, segment 1 is used and the
following settings must be carried out.
Example 3:
An SFC-Cl
2
is installed with an MFC setpoint trim. The Cl
2
measurement is transmitted from the SFC to the MFC via CAN.
The following table lists possible settings for the MFC and SFC.
The measurements are transmitted in segment 1 to address 2.
A bus end (bus termination Rt) must be installed at the first and last
units in the bus. The MFC is equipped with a RT dip switch. Other
units (dip switch number 4 on switch block between terminals 22
and 23) require a menu setting that activates the bus termination.
Balancing of the CAN bus must take place once in the CAN bus.
However, the MFC does not offer this option.
SFC-Cl
2
++:
Menu - Input/Output - Interface - "CAN
segment"
1
Menu - Cl
2
++ - Measuring range -
"CAN address pH“"
2
MFC-pH:
Menu - pH - Meas.range
"CAN
seg. MV->“
1
Menu - pH - Meas.range
"CAN
addr. MV->"
2
MFC-Cl
2
:
Menu - Input/Output - Interface - "CAN
segment":
1
Menu - Mod 2 - Meas.range - "CAN
addr.MV"
2
SFC-Cl
2
:
Menu - Input/Output - Interface - "CAN
seg. MV->“
1
Menu - Input/Output - Interface - "CAN
addr. MV->"
2
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...