Functions
MFC
4.
Special Functions
•
The control direction can be switched.
•
Automatic determination of the control parameter using the
integrated fuzzy module. The fuzzy module determines the
control parameter from the embedded Tconst and Tvar
process times.
•
The setpoint can be switched between internal and external
•
Ypi stop function during a change in control variable
•
Control variable Wq available optionally as proportional or
indirect proportional as well as factor adjustment
•
Smooth switch from compound-loop-control to single feed
forward control or single feed back control via digital input 1, 2
or 3 available
Yout = Wq x (DF
Wq
+ ek x Kp x (1 + t/tn)) x Yout-factor
Ratio
Feedback
control
t
Internal controller cycle time
tn
Integral action time
Kp
Control amplification 100 / Xp
ek
Setpoint-actual value control deviation
DF
Wq
Learned dosing factor for the current flow rate
Wq
Flow rate signal in %
Yout
Determined controller output value %
Yout factor
This factor offers the option to increase the dosing
output if the setpoint is not reached with a dosing
factor DF of 100 %.
Setting range: 1.0– 4.0
Factory setting: 1.0
Determining combi-
control process times
To adjust the control for compound-loop-control, the Tconst and
Tvar process times must bet entered in the parameter menu path.
These times refer to control loop dead times,which on the one
hand are independent of the control variables, and on the other
hand depend proportionally on the control variables.
The constant dead time< Tconst > (independent of control
variable) consists of the control variable measurement dead time
(measuring dead time) and possible dosing delays.
The variable dead time< Tvar > depends on the current control
variable and is entered in the menu at a control variable of 100%.
The following calculation examples apply for the use of the MFC
for flow-controlled chlorine dosing with chlorine overfeed
correction (potable water control loop).
Note:
If this factor is increased, there is a danger that the
setpoint value will also not be reached with a higher
flow rate value, because the Yout value takes the value
100 % prematurely.
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...