16
WT.050.580.000.DE.IM.0714
Description
MFC
3.
DES module
Membrane sensors
Sensor:
3 electrode sensor
membrane-covered
Principle of operation:
Potentiostatic amperometry
Temperature drift
max. 0.2 % / 10 K
Linearity error:
< 0.1 %
Calibration:
pre-calibrated
Input signal
(plug-in card):
-7 to 1000 µA cell current
pH measuring module
for pH value
Sensor input:
pH single-rod electrode
Temperature drift
max. 0.2 % / 10 K
Linearity error:
< 0.1 %
Calibration:
pre-calibrated
Input signal
-1000 to +1000 mV
Input impedance:
10
13
Ohm
mV measuring module
for Redox
Sensor input:
Redox single-rod electrode
Temperature drift
max. 0.2 % / 10 K
Linearity error:
< 0,1 %
Calibration:
pre-calibrated
Input signal
-1000 to +1000 mV
Input impedance:
10
13
Ohm
mS measuring module
for conductivity
Sensor input:
LF325
Temperature measuring range:
0 to +50 °C
Temperature drift:
< 0.2 %
Calibration:
pre-calibrated
Linearity error:
< 0.5 %
Measuring ranges:
2500 µS/cm,
10, 20, 50, 100, 200 mS/cm
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...