MFC
Operation
5.
133
Timer setting
Timer Contact 1
Selection of 9 on-duty and
and off-duty cycles max.
Timer Contact 2
Selection of 9 on-duty and
and off-duty cycles max.
Setpoint trim
Trim setpoint
Switch on/off
Trim factor
0–100 %
Setpoint range
5–50 %
Xsh 1–10
%
Tconst
30 s – 10 h
Tvar
30 s – 10 h
Measuring range
See module type 1 under ““Measuring range" on page 126:
CAN address
00...31 (-- off)
Defines the CAN bus address of the
external measurement in application 5
(setpoint trim)
Limit values
Min
within measuring range
Max
within measuring range
Hysteresis
Depends on measuring range
0.01 to 0.25 / 00.1 to 05.0 / 1 to 50
Adaption
Adaption is only available for single feedback closed-loop control
with "DES" modules.
Tu 1–3600
s
Ts
0.1 to 480.0 min
1
:
00:00
-
00:00
--
Switching
cycle 1-9
Duty
cycle
hh:mm
Off-duty
cycle
hh:mm
Day Mo-Su
(If "--" is
displayed,
the
switching
cycle is
inactive)
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...