MFC
Description
3.
13
3. Description
3.1
Technical Data
3.1.1
MFC electronic module
Housing
Dimensions (W x H x D):
320 x 270 x 175 mm
Weight:
approx. 5 kg
Protection category:
IP 66
Electronics
Mains connection
•
200–240 V AC ± 10 %, 50–60 Hz, 30 VA,
Fuse 1A (T) Type: TR5
•
100–120 V AC ± 10 %, 50–60 Hz, 30 VA,
Fuse 1A (T) Type: TR5
•
24 V DC ± 20 %, 30 W, Fuse 2.5 A (T) Type: TR5
Insulation
•
Overvoltage category
2
•
Contamination level
2
Operating conditions
•
Ambient temperature
0–50 °C
•
Humidity
< 80 %, non-condensing
•
Environment
No direct sunlight
•
Atmospheric pressure
75–106 kPa
•
max. altitude
2000 m
•
Storage temperature
-20 to +70 °C
•
Noise emission
<45 dB
Digital inputs
3 x for floating contact (< 100 Ohm)
Power supply though MFC
•
D1: Sample water monitoring (freely selectable)
•
D2: Freely selectable in menu
•
D3: Freely selectable in menu