MFC
Functions
4.
79
The controller output is calculated in this operating mode as
follows:
Yout = Wq x DF x (X-measured value x X-factor) x Yout-factor
Wq
Control variable 1 flow in %
DF
Set dosing factor in %
X-measured value
Control variable 2 measured value sensor
measuring module 1 in %
X factor
Amplification factor for X measured value
Yout
Determined controller output value %
Yout factor
This factor offers the option to increase the dosing
output if the setpoint is not reached with a dosing
factor DF of 100 %.
Setting range: 1.0– 4.0
Factory setting: 1.0
4.5.2
Single Feed Back Control
This operating mode controls the desired measured variable
according to the the provided setpoint.
A typical application example is chlorine control for tanks that are
circulated in cycles.
Please note
This control operating mode is also available for sensor measuring
module 2 if application 3 is selected, however, only with internal
setpoint input.
Note:
If this factor is increased, there is a danger that
the setpoint value will also not be reached with a
higher flow rate value, because the Yout value
takes the value 100 % prematurely.
mg/l
6,85
705
0,00
1.00
0.43
4.00
9.00
7.00
400
pH
mV
900
0,65
12:35
Kreis 1
100% 28°C
MODE
CAL
MENU
mA ?
DI
I
DI
II
DI
III
ESC
control output
Dosing device
positioner, pumps
Sensors
+Temp.
Flow
sensor
Q
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...