28
WT.050.580.000.DE.IM.0714
Description
MFC
3.
Water quality:
Clean water, potable water
quality (limestone deposits
may block the membranes)
a membrane sensor for total
chlorine TC1-S is available for
brine
Conductivity:
with standard electrolyte
W3T171793 <2500 µS/cm
with brine electrolyte
W3T164805
2,5 à 60 mS/cm
Flow:
6–35 l/h, as constant as
possible
Service life:
Life of the electrolytes in
operation approx. 6 months,
service life of membrane cap
typically 1 year (reduced by poor
water quality, e.g. sand, filth)
Cross-sensitivity:
Ozone, bromine, chlorine
dioxide, hydrogen peroxide
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...