4.
97
Tu
Meaning:
Loop dead time
Display:
Seconds (s)
Explanation:
Time required between dosing start and clear recognition of the
rise in the control variable
Setting range:
The parameter Tu can be set from 1 s – 59 min 59s.
Please note
If the values Tu and Ts are manually modified, the control
parameters Xp and Tn are re-calculated.
Ty
Meaning:
Running time of the positioner
Display:
Seconds (s)
Explanation:
The parameter Ty only applies to positioners.
Ty is the time which the positioner requires to adjust from 0 % to
100 %.
Setting range:
The parameter Ty can be set from 10–180 s.
Control direction
Meaning:
Direction of the control
Display:
Direct/inverse (e.g. for pH)
Explanation:
Defines which medium is used to perform the correction.
Example:
pH:
Control direction "inverse": Lowering pH-value by
adding acid
pH:
Control direction "direct": Adding alkaline to raise
the pH value