Position.Ym?
Ym range too narrow
Position 0 % or 100 % incorrectly
calibrated
Set gap between 0 % and 100 % to at
least 60 % of the entire path
Positioner selected, but not
connected
Check setting: Positioner with Ym
Feedback signal incorrect
Check feedback signal (1kOhm)
Positioner feedback incorrectly
connected or defective
Check (refer to 9. “Wiring Diagrams" on
page 245)
Module?
Sensor module was removed
Sensor module defective
Refit or replace the sensor module
Adaption?
Adaption terminated with error
Refer to 4.9 “Adaption" on page 104
Measuring range 1?
Measuring range 2?
Measuring range 3?
Measuring range 4?
Min. or max. limit value is outside
the measuring range
Check the min/max limit values and
change, if necessary
Setpoint trim?
Measuring range and unit for Mod 1
and Mod two not identical
Set measuring range and unit for Mod 1
the same, e.g.
Mod 1 = 1.00 mg/l
Mod 2 = 1.00 mg/l
Error message
Cause
Remedy
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...